Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2010-01-01 → 2010-03-31 |
| MCL | Health-based | Resolved | 2010-01-01 → 2010-03-31 |
| MCL | Health-based | Resolved | 2010-01-01 → 2010-03-31 |
| MCL | Health-based | Resolved | 2010-01-01 → 2010-03-31 |
| MCL | Health-based | Resolved | 2009-10-01 → 2009-12-31 |
| MCL | Health-based | Resolved | 2009-10-01 → 2009-12-31 |
| MCL | Health-based | Resolved | 2009-10-01 → 2009-12-31 |
| MCL | Health-based | Resolved | 2009-10-01 → 2009-12-31 |
| MCL | Health-based | Resolved | 2009-07-01 → 2009-09-30 |
| MCL | Health-based | Resolved | 2009-07-01 → 2009-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 27.3 µg/L No EPA limit set | 44/45 | SYR4 | 2012–2019 |
| Chloroform | 48.8 µg/L No EPA limit set | 44/45 | SYR4 | 2012–2019 |
| Dibromochloromethane | 30.6 µg/L No EPA limit set | 44/45 | SYR4 | 2012–2019 |
| TTHM | 91.7 µg/L 115% of the EPA limit, in the worst sample — 80 µg/L | 43/45 | SYR4 | 2012–2019 |
| Bromoform | 8.18 µg/L No EPA limit set | 37/45 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 5.83 µg/L No EPA limit set | 34/34 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 18.6 µg/L No EPA limit set | 34/34 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 34.5 µg/L 57% of the EPA limit 60 µg/L | 34/34 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 9.52 µg/L No EPA limit set | 34/34 | SYR4 | 2012–2019 |
| Nitrate | 514 µg/L 5.1% of the EPA limit 10000 µg/L | 18/18 | SYR4 | 2012–2018 |
| Fluoride | 317 µg/L 7.9% of the EPA limit 4000 µg/L | 10/10 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2024 |
| Barium | 125 µg/L 6.3% of the EPA limit 2000 µg/L | 9/9 | SYR4 | 2012–2019 |
| Copper | 338 µg/L 26% of the EPA limit 1300 µg/L | 9/9 | SYR4 | 2012–2019 |
| Selenium | 6.49 µg/L 13% of the EPA limit 50 µg/L | 9/9 | SYR4 | 2012–2019 |
| Arsenic | 3.94 µg/L 39% of the EPA limit 10 µg/L | 8/9 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 514 µg/L 5.1% of the EPA limit 10000 µg/L | 7/7 | SYR4 | 2012–2018 |
| Monobromoacetic Acid | 3.79 µg/L No EPA limit set | 6/34 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.55 µg/L No EPA limit set | 5/34 | SYR4 | 2012–2019 |
| Chromium | 6.05 µg/L 6.1% of the EPA limit 100 µg/L | 4/9 | SYR4 | 2012–2019 |
| Dalapon | 1.14 µg/L 0.6% of the EPA limit 200 µg/L | 3/7 | SYR4 | 2012–2019 |
| Antimony, Total | 3 µg/L 50% of the EPA limit 6 µg/L | 2/9 | SYR4 | 2012–2019 |
| Combined Uranium | 4.23 µg/L 14% of the EPA limit 30 µg/L | 2/2 | SYR4 | 2013–2016 |
| Xylenes, Total | 14.5 µg/L 0.1% of the EPA limit 10000 µg/L | 2/13 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2016 |
| Ethylbenzene | 1.65 µg/L 0.2% of the EPA limit 700 µg/L | 1/13 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 1.77 pCi/L No EPA limit set | 1/1 | SYR4 | 2016 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Nps Callville Bay
Is Nps Callville Bay tap water safe to drink?
EPA monitoring detected 27 contaminants in Nps Callville Bay's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Nps Callville Bay's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Bromoform, and others. The full list with the level and data source for each is above.
How many people does Nps Callville Bay serve?
Nps Callville Bay reports serving 250 people in Nevada, per its EPA record.
Has Nps Callville Bay had any water quality violations?
The EPA has 114 violations on file for Nps Callville Bay, of which 46 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.