← New Jersey

Tap water quality report

Holly Tree Acres System 1

EPA monitoring tested this supplier for 67 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

67
contaminants tested
20
detected
300
people served
21
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Salem

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

21
health-based violations
150
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
16200 µg/L 162%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 17350 µg/L
58/76 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
22/22 LCR 2025
Copper
168 µg/L 13%
of the EPA limit 1300 µg/L
worst single sample: 206 µg/L
11/47 SYR4 2012–2019
Chloroform
163.185 µg/L
No EPA limit set
worst single sample: 285 µg/L
10/20 SYR4 2012–2019
Barium
128.7 µg/L 6.4%
of the EPA limit 2000 µg/L
worst single sample: 135 µg/L
7/7 SYR4 2012–2018
Combined Radium (-226 And -228)
4.45 pCi/L 89%
of the EPA limit 5 pCi/L
worst single sample: 4.9 pCi/L
6/6 SYR4 2012–2018
Lead
11.52 µg/L 77%
of the EPA limit 15 µg/L
worst single sample: 12.4 µg/L
5/40 SYR4 2012–2019
Bromodichloromethane
6.795 µg/L
No EPA limit set
worst single sample: 7.2 µg/L
4/20 SYR4 2012–2019
Dibromochloromethane
3.825 µg/L
No EPA limit set
worst single sample: 3.9 µg/L
2/7 SYR4 2012–2019
TTHM
24.995 µg/L 31%
of the EPA limit 80 µg/L
worst single sample: 25.4 µg/L
2/4 SYR4 2019
Cadmium
0.1830 µg/L 3.7%
of the EPA limit 5 µg/L
1/7 SYR4 2012–2018
Dibromoacetic Acid
1.2 µg/L
No EPA limit set
1/2 SYR4 2019
Dichloroacetic Acid
5.5 µg/L
No EPA limit set
1/2 SYR4 2019
Fluoride
420 µg/L 11%
of the EPA limit 4000 µg/L
1/8 SYR4 2012–2018
Mercury
0.0530 µg/L 2.7%
of the EPA limit 2 µg/L
1/7 SYR4 2012–2018
Monochloroacetic Acid
2.2 µg/L
No EPA limit set
1/2 SYR4 2019
Thallium, Total
0.8000 µg/L 40%
of the EPA limit 2 µg/L
1/7 SYR4 2012–2018
Toluene
1.3 µg/L 0.1%
of the EPA limit 1000 µg/L
1/18 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
13.6 µg/L 23%
of the EPA limit 60 µg/L
1/2 SYR4 2019
Trichloroacetic Acid
4.7 µg/L
No EPA limit set
1/2 SYR4 2019
47 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCarbon TetrachlorideChromiumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
RUSSO, JAYNA
Phone
443-924-0547
Email
JRUSSO.HORIZONLANDCO.COM

Frequently asked questions about Holly Tree Acres System 1

Is Holly Tree Acres System 1 tap water safe to drink?

EPA monitoring detected 20 contaminants in Holly Tree Acres System 1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Holly Tree Acres System 1's water?

EPA monitoring detected Nitrate, Lead, Copper, Chloroform, Barium, and others. The full list with the level and data source for each is above.

How many people does Holly Tree Acres System 1 serve?

Holly Tree Acres System 1 reports serving 300 people in New Jersey, per its EPA record.

Has Holly Tree Acres System 1 had any water quality violations?

The EPA has 150 violations on file for Holly Tree Acres System 1, of which 21 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.