← New Jersey

Tap water quality report

High Bridge W Dept

EPA monitoring tested this supplier for 97 contaminants and detected 32. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

97
contaminants tested
32
detected
3,300
people served
8
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Hunterdon

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
139
violations on file
3
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2014-08-01 → 2014-08-31
MCL Health-based Resolved 2014-08-01 → 2014-08-31
MCL Health-based Resolved 2014-08-01 → 2014-08-31
MCL Health-based Resolved 1996-01-01 → 1996-12-31
MCL Health-based Resolved 1995-01-01 → 1995-12-31
MCL Health-based Resolved 1995-01-01 → 1995-12-31
MCL Health-based Resolved 1995-01-01 → 1995-12-31
MCL Health-based Resolved 1995-01-01 → 1995-12-31
Other Monitoring Resolved 2025-07-01
Other Monitoring Resolved 2025-07-01

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFOA 0.0049 µg/L 2/4 2023
PFOS 0.0048 µg/L 2/4 2023
PFBS 0.0030 µg/L 1/4 2023

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
352 µg/L 27%
of the EPA limit 1300 µg/L
worst single sample: 783 µg/L
86/86 SYR4 2012–2018
Chloroform
3.052 µg/L
No EPA limit set
worst single sample: 175 µg/L
83/111 SYR4 2012–2019
Lead
6.63 µg/L 44%
of the EPA limit 15 µg/L
worst single sample: 11.5 µg/L
80/80 SYR4 2012–2017
Dibromochloromethane
3.056 µg/L
No EPA limit set
worst single sample: 8.54 µg/L
69/111 SYR4 2012–2019
Bromodichloromethane
3.13 µg/L
No EPA limit set
worst single sample: 4.24 µg/L
68/111 SYR4 2012–2019
Bromoform
2.52 µg/L
No EPA limit set
worst single sample: 4.62 µg/L
41/111 SYR4 2012–2019
Nitrate
2612 µg/L 26%
of the EPA limit 10000 µg/L
worst single sample: 2700 µg/L
32/32 SYR4 2012–2019
Lead
0.0042 mg/L 28%
of the EPA limit 0.0150 mg/L
26/26 LCR 2023
TTHM
11.4325 µg/L 14%
of the EPA limit 80 µg/L
worst single sample: 13.33 µg/L
16/16 SYR4 2012–2019
Arsenic
1.5625 µg/L 16%
of the EPA limit 10 µg/L
worst single sample: 1.8 µg/L
6/6 SYR4 2012–2018
Barium
77.25 µg/L 3.9%
of the EPA limit 2000 µg/L
worst single sample: 79.2 µg/L
6/6 SYR4 2012–2018
Dichloroacetic Acid
2.17 µg/L
No EPA limit set
worst single sample: 2.47 µg/L
6/16 SYR4 2012–2019
Selenium
2.425 µg/L 4.9%
of the EPA limit 50 µg/L
worst single sample: 2.5 µg/L
6/6 SYR4 2012–2018
Total Haloacetic Acids (HAA5)
4.775 µg/L 8%
of the EPA limit 60 µg/L
worst single sample: 5.5 µg/L
6/16 SYR4 2012–2019
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
4/4 SYR4 2012–2018
Dibromoacetic Acid
1.719 µg/L
No EPA limit set
worst single sample: 1.74 µg/L
4/16 SYR4 2012–2019
Chromium
3.74 µg/L 3.7%
of the EPA limit 100 µg/L
worst single sample: 3.9 µg/L
3/6 SYR4 2012–2018
Mercury
0.0579 µg/L 2.9%
of the EPA limit 2 µg/L
worst single sample: 0.0580 µg/L
3/6 SYR4 2012–2018
Thallium, Total
0.0680 µg/L 3.4%
of the EPA limit 2 µg/L
worst single sample: 0.0700 µg/L
2/6 SYR4 2012–2018
1,1,1-Trichloroethane
6.94 µg/L 3.5%
of the EPA limit 200 µg/L
1/95 SYR4 2012–2019
Benzene
0.0900 µg/L 1.8%
of the EPA limit 5 µg/L
1/95 SYR4 2012–2019
Cadmium
0.0200 µg/L 0.4%
of the EPA limit 5 µg/L
1/6 SYR4 2012–2018
Carbon Tetrachloride
0.3100 µg/L 6.2%
of the EPA limit 5 µg/L
1/95 SYR4 2012–2019
Ethylbenzene
0.1300 µg/L 0%
of the EPA limit 700 µg/L
1/95 SYR4 2012–2019
Fluoride
270 µg/L 6.8%
of the EPA limit 4000 µg/L
1/12 SYR4 2012–2018
Monobromoacetic Acid
0.5700 µg/L
No EPA limit set
1/16 SYR4 2012–2019
Toluene
0.1800 µg/L 0%
of the EPA limit 1000 µg/L
1/95 SYR4 2012–2019
Trichloroacetic Acid
0.7200 µg/L
No EPA limit set
1/16 SYR4 2012–2019
Xylenes, Total
0.3600 µg/L 0%
of the EPA limit 10000 µg/L
1/95 SYR4 2012–2019
65 contaminants tested, none detected
1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonochloroacetic AcidNetfosaaNfdhaNmefosaaPfbaPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
METZ, BRANDON
Phone
908-638-6588

Frequently asked questions about High Bridge W Dept

Is High Bridge W Dept tap water safe to drink?

EPA monitoring detected 32 contaminants in High Bridge W Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in High Bridge W Dept's water?

EPA monitoring detected Copper, Chloroform, Lead, Dibromochloromethane, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does High Bridge W Dept serve?

High Bridge W Dept reports serving 3,300 people in New Jersey, per its EPA record.

Has High Bridge W Dept had any water quality violations?

The EPA has 139 violations on file for High Bridge W Dept, of which 8 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.