← New Jersey

Tap water quality report

Nj American Water - Logan

EPA monitoring tested this supplier for 84 contaminants and detected 25. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

84
contaminants tested
25
detected
6,650
people served
0
health-based violations
Water source
SWP
Ownership
Private
Counties served
Gloucester

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
40
violations on file
0
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2016-07-01
Other Monitoring Resolved 2016-07-01
MR Monitoring Resolved 2009-01-01 → 2009-12-31
MR Monitoring Resolved 2009-01-01 → 2009-12-31
MR Monitoring Resolved 2009-01-01 → 2009-12-31
MR Monitoring Resolved 2009-01-01 → 2009-12-31
MR Monitoring Resolved 2009-01-01 → 2009-12-31
MR Monitoring Resolved 2009-01-01 → 2009-12-31
MR Monitoring Resolved 2005-04-01 → 2005-04-30
MR Monitoring Resolved 2005-04-01 → 2005-04-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfhxa 0.0048 µg/L 3/8 2025
Pfpea 0.0049 µg/L 3/8 2025
PFOA 0.0042 µg/L 2/8 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
618 µg/L 48%
of the EPA limit 1300 µg/L
70/78 SYR4 2012–2018
Bromodichloromethane
16.6 µg/L
No EPA limit set
64/64 SYR4 2012–2019
Chloroform
51.8 µg/L
No EPA limit set
64/64 SYR4 2012–2019
Dibromochloromethane
12.4 µg/L
No EPA limit set
64/64 SYR4 2012–2019
TTHM
68.8 µg/L 86%
of the EPA limit 80 µg/L
64/64 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
37 µg/L 62%
of the EPA limit 60 µg/L
64/64 SYR4 2012–2019
Dichloroacetic Acid
24 µg/L
No EPA limit set
63/64 SYR4 2012–2019
Trichloroacetic Acid
16 µg/L
No EPA limit set
63/64 SYR4 2012–2019
Bromoform
2.7 µg/L
No EPA limit set
38/64 SYR4 2012–2019
Dibromoacetic Acid
3 µg/L
No EPA limit set
36/64 SYR4 2012–2019
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
17/17 LCR 2024
Nitrate
3820 µg/L 38%
of the EPA limit 10000 µg/L
16/30 SYR4 2012–2019
Nitrate-Nitrite
3820 µg/L 38%
of the EPA limit 10000 µg/L
8/15 SYR4 2012–2019
Monobromoacetic Acid
15.4 µg/L
No EPA limit set
7/64 SYR4 2012–2019
Fluoride
140 µg/L 3.5%
of the EPA limit 4000 µg/L
5/15 SYR4 2012–2018
Lead
23 µg/L 153%
of the EPA limit, in the worst sample — 15 µg/L
5/73 SYR4 2012–2018
Monochloroacetic Acid
3.6 µg/L
No EPA limit set
4/64 SYR4 2012–2019
Lithium
17.2 µg/L
No EPA limit set
4/8 UCMR-5 2024
Beryllium, Total
1 µg/L 25%
of the EPA limit 4 µg/L
3/8 SYR4 2012–2018
Combined Radium (-226 And -228)
3.89 pCi/L 78%
of the EPA limit 5 pCi/L
3/4 SYR4 2012–2018
Gross Alpha, Excl. Radon And U
9.9 pCi/L 66%
of the EPA limit 15 pCi/L
2/3 SYR4 2012–2018
Barium
100 µg/L 5%
of the EPA limit 2000 µg/L
1/8 SYR4 2012–2018
59 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicBenzeneChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumCombined UraniumDichloromethaneEthylene DibromideEthylbenzeneHfpo-DaMercuryNetfosaaNfdhaNmefosaaNitritePfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOSPfpesPftaPftrdaPfunaSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
ROSSI, GREG
Phone
856-764-4932

Frequently asked questions about Nj American Water - Logan

Is Nj American Water - Logan tap water safe to drink?

EPA monitoring detected 25 contaminants in Nj American Water - Logan's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Nj American Water - Logan's water?

EPA monitoring detected Copper, Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.

How many people does Nj American Water - Logan serve?

Nj American Water - Logan reports serving 6,650 people in New Jersey, per its EPA record.

Has Nj American Water - Logan had any water quality violations?

The EPA has 40 violations on file for Nj American Water - Logan, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.