Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| RPT | Monitoring | Resolved | 2024-11-12 |
| RPT | Monitoring | Resolved | 2024-11-12 |
| RPT | Monitoring | Resolved | 2024-11-12 |
| RPT | Monitoring | Resolved | 2024-11-12 |
| MON | Monitoring | Resolved | 2024-10-01 → 2024-11-01 |
| MON | Monitoring | Resolved | 2024-10-01 → 2024-11-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 60.1 µg/L 4.6% of the EPA limit 1300 µg/L
worst single sample: 68.2 µg/L | 11/12 | SYR4 | 2015–2019 |
| Lead | 3.065 µg/L 20% of the EPA limit 15 µg/L
worst single sample: 3.1 µg/L | 8/11 | SYR4 | 2015–2019 |
| Combined Radium (-226 And -228) | 150.2 pCi/L 3004% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 166 pCi/L | 3/5 | SYR4 | 2017–2018 |
| Barium | 27.697 µg/L 1.4% of the EPA limit 2000 µg/L
worst single sample: 29 µg/L | 2/2 | SYR4 | 2016–2019 |
| Combined Uranium | 3.465 µg/L 12% of the EPA limit 30 µg/L
worst single sample: 3.5 µg/L | 2/3 | SYR4 | 2017 |
| Gross Alpha, Excl. Radon And U | 10.225 pCi/L 68% of the EPA limit 15 pCi/L
worst single sample: 10.6 pCi/L | 2/3 | SYR4 | 2017 |
| Fluoride | 226 µg/L 5.7% of the EPA limit 4000 µg/L | 1/2 | SYR4 | 2016–2019 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about Mill Pond Crossing
Is Mill Pond Crossing tap water safe to drink?
EPA monitoring detected 7 contaminants in Mill Pond Crossing's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Mill Pond Crossing's water?
EPA monitoring detected Copper, Lead, Combined Radium (-226 And -228), Barium, Combined Uranium, and others. The full list with the level and data source for each is above.
How many people does Mill Pond Crossing serve?
Mill Pond Crossing reports serving 72 people in New Hampshire, per its EPA record.
Has Mill Pond Crossing had any water quality violations?
The EPA has 12 violations on file for Mill Pond Crossing, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.