← Nebraska

Tap water quality report

Harrisburg Water

EPA monitoring tested this supplier for 68 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

68
contaminants tested
11
detected
150
people served
20
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Banner

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

20
health-based violations
23
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2015-12-01 → 2015-12-31
MCL Health-based Resolved 2015-12-01 → 2015-12-31
MCL Health-based Resolved 2015-12-01 → 2015-12-31
MCL Health-based Resolved 2015-12-01 → 2015-12-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-10-01 → 2011-10-31
MCL Health-based Resolved 2011-09-01 → 2011-09-30
MCL Health-based Resolved 2011-09-01 → 2011-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate-Nitrite
2240 µg/L 22%
of the EPA limit 10000 µg/L
worst single sample: 2250 µg/L
48/48 SYR4 2012–2019
Arsenic
6.6475 µg/L 66%
of the EPA limit 10 µg/L
worst single sample: 6.94 µg/L
10/10 SYR4 2012–2019
Copper
33.54 µg/L 2.6%
of the EPA limit 1300 µg/L
worst single sample: 36.5 µg/L
9/10 SYR4 2014–2017
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
9/9 LCR 2023
Barium
148.2 µg/L 7.4%
of the EPA limit 2000 µg/L
worst single sample: 150 µg/L
7/7 SYR4 2012–2018
Fluoride
536.9 µg/L 13%
of the EPA limit 4000 µg/L
worst single sample: 539 µg/L
7/7 SYR4 2012–2018
Lead
1.1935 µg/L 8%
of the EPA limit 15 µg/L
worst single sample: 1.21 µg/L
4/10 SYR4 2014–2017
Chromium
3.401 µg/L 3.4%
of the EPA limit 100 µg/L
worst single sample: 3.57 µg/L
3/7 SYR4 2012–2018
Combined Radium (-226 And -228)
0.6349 pCi/L 13%
of the EPA limit 5 pCi/L
worst single sample: 0.6630 pCi/L
2/6 SYR4 2012–2018
1,2-Dichloroethane
2.42 µg/L 48%
of the EPA limit 5 µg/L
1/10 SYR4 2012–2018
Dichloromethane
1.49 µg/L 30%
of the EPA limit 5 µg/L
1/10 SYR4 2012–2018
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromochloromethaneDinosebDiquatEthylene DibromideEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SCHANEMAN, SCOTT
Phone
308-632-2749
Email
sschaneman@npnrd.org

Frequently asked questions about Harrisburg Water

Is Harrisburg Water tap water safe to drink?

EPA monitoring detected 11 contaminants in Harrisburg Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Harrisburg Water's water?

EPA monitoring detected Nitrate-Nitrite, Arsenic, Copper, Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does Harrisburg Water serve?

Harrisburg Water reports serving 150 people in Nebraska, per its EPA record.

Has Harrisburg Water had any water quality violations?

The EPA has 23 violations on file for Harrisburg Water, of which 20 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.