Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2024-10-01 → 2024-12-31 |
| MCL | Health-based | Resolved | 2024-10-01 → 2024-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Combined Uranium | 43.2845 µg/L 144% of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 48.127 µg/L | 6/16 | SYR4 | 2012–2019 |
| Nitrate | 3390 µg/L 34% of the EPA limit 10000 µg/L | 6/42 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 3.82 pCi/L 76% of the EPA limit 5 pCi/L
worst single sample: 3.9 pCi/L | 5/8 | SYR4 | 2012–2019 |
| Copper | 185.55 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 198 µg/L | 4/40 | SYR4 | 2012–2019 |
| Fluoride | 264 µg/L 6.6% of the EPA limit 4000 µg/L
worst single sample: 280 µg/L | 3/8 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 23.94 pCi/L 160% of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 26 pCi/L | 3/6 | SYR4 | 2016–2019 |
| Nitrate-Nitrite | 3359 µg/L 34% of the EPA limit 10000 µg/L
worst single sample: 3390 µg/L | 3/12 | SYR4 | 2016–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 2/2 | LCR | 2025 |
| Chloroform | 3 µg/L No EPA limit set | 1/4 | SYR4 | 2016–2019 |
| Dichloroacetic Acid | 2 µg/L No EPA limit set | 1/4 | SYR4 | 2016–2019 |
| TTHM | 3 µg/L 3.8% of the EPA limit 80 µg/L | 1/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 2 µg/L 3.3% of the EPA limit 60 µg/L | 1/7 | SYR4 | 2013–2019 |
66 contaminants tested, none detected
Utility contact
Frequently asked questions about Southern Trace S/D
Is Southern Trace S/D tap water safe to drink?
EPA monitoring detected 12 contaminants in Southern Trace S/D's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Southern Trace S/D's water?
EPA monitoring detected Combined Uranium, Nitrate, Combined Radium (-226 And -228), Copper, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Southern Trace S/D serve?
Southern Trace S/D reports serving 485 people in North Carolina, per its EPA record.
Has Southern Trace S/D had any water quality violations?
The EPA has 301 violations on file for Southern Trace S/D, of which 44 are health-based (a contaminant limit or required treatment was breached) and 16 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.