← North Carolina

Tap water quality report

Longleaf Neuro-Medical Treatment Center

EPA monitoring tested this supplier for 15 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

15
contaminants tested
14
detected
200
people served
2
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Wilson

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
59
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
MR Monitoring Resolved 2026-03-01 → 2026-03-31
MR Monitoring Resolved 2026-03-01 → 2026-03-31
MR Monitoring Resolved 2026-03-01 → 2026-03-31
MR Monitoring Resolved 2026-03-01 → 2026-03-31
MR Monitoring Resolved 2026-03-01 → 2026-03-31
MR Monitoring Resolved 2026-02-01 → 2026-02-28
MR Monitoring Resolved 2026-02-01 → 2026-02-28
MR Monitoring Resolved 2026-02-01 → 2026-02-28

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chlorite
690 µg/L 69%
of the EPA limit 1000 µg/L
135/139 SYR4 2016–2019
Copper
1582 µg/L 122%
of the EPA limit, in the worst sample — 1300 µg/L
41/80 SYR4 2016–2019
Bromodichloromethane
19.3 µg/L
No EPA limit set
14/14 SYR4 2016–2019
Chloroform
84.1 µg/L
No EPA limit set
14/14 SYR4 2016–2019
Dichloroacetic Acid
30.5 µg/L
No EPA limit set
14/14 SYR4 2016–2019
TTHM
101.9 µg/L 127%
of the EPA limit, in the worst sample — 80 µg/L
14/14 SYR4 2016–2019
Total Haloacetic Acids (HAA5)
69 µg/L 115%
of the EPA limit, in the worst sample — 60 µg/L
14/14 SYR4 2016–2019
Trichloroacetic Acid
34.9 µg/L
No EPA limit set
14/14 SYR4 2016–2019
Dibromochloromethane
3.1 µg/L
No EPA limit set
12/14 SYR4 2016–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
10/10 LCR 2025
Lead
13 µg/L 87%
of the EPA limit 15 µg/L
5/80 SYR4 2016–2019
Monobromoacetic Acid
10 µg/L
No EPA limit set
3/14 SYR4 2016–2019
Monochloroacetic Acid
3.6 µg/L
No EPA limit set
3/14 SYR4 2016–2019
Dibromoacetic Acid
1 µg/L
No EPA limit set
1/14 SYR4 2016–2019
1 contaminants tested, none detected
Bromoform

Utility contact

Contact
SEARS, DANIEL
Email
dsears@envirolinkinc.com

Frequently asked questions about Longleaf Neuro-Medical Treatment Center

Is Longleaf Neuro-Medical Treatment Center tap water safe to drink?

EPA monitoring detected 14 contaminants in Longleaf Neuro-Medical Treatment Center's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Longleaf Neuro-Medical Treatment Center's water?

EPA monitoring detected Chlorite, Copper, Bromodichloromethane, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Longleaf Neuro-Medical Treatment Center serve?

Longleaf Neuro-Medical Treatment Center reports serving 200 people in North Carolina, per its EPA record.

Has Longleaf Neuro-Medical Treatment Center had any water quality violations?

The EPA has 59 violations on file for Longleaf Neuro-Medical Treatment Center, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.