Johnson & Son Mhp

EPA monitoring tested this supplier for 76 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

76
contaminants tested
10
detected
102
people served
13
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Wake

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

13
health-based violations
197
violations on file
2
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 1999-06-01 → 1999-06-30
MCL Health-based Resolved 1999-06-01 → 1999-06-30
MCL Health-based Resolved 1999-06-01 → 1999-06-30
MCL Health-based Resolved 1999-06-01 → 1999-06-30
MCL Health-based Archived 1983-06-24 → 1984-09-23
MCL Health-based Archived 1983-06-24 → 1984-09-23
MCL Health-based Archived 1983-06-24 → 1984-09-23
MCL Health-based Archived 1983-06-24 → 1984-09-23

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
2800 µg/L 28%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Copper
92.5 µg/L 7.1%
of the EPA limit 1300 µg/L
worst single sample: 94 µg/L
11/25 SYR4 2012–2019
Combined Uranium
20.1895 µg/L 67%
of the EPA limit 30 µg/L
worst single sample: 20.264 µg/L
3/3 SYR4 2013–2019
Fluoride
345 µg/L 8.6%
of the EPA limit 4000 µg/L
worst single sample: 350 µg/L
3/3 SYR4 2013–2019
Nitrate-Nitrite
2760 µg/L 28%
of the EPA limit 10000 µg/L
worst single sample: 2800 µg/L
3/3 SYR4 2013–2015
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
2/2 LCR 2025
Lead
4.95 µg/L 33%
of the EPA limit 15 µg/L
worst single sample: 5 µg/L
2/25 SYR4 2012–2019
Barium
18 µg/L 0.9%
of the EPA limit 2000 µg/L
1/3 SYR4 2013–2019
Chloroform
1.1 µg/L
No EPA limit set
1/3 SYR4 2013–2017
TTHM
1.1 µg/L 1.4%
of the EPA limit 80 µg/L
1/3 SYR4 2013–2017
66 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDibromochloromethaneDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)Total Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
JOHNSON, RACHEL
Email
rsoapoperamom@aol.com

Frequently asked questions about Johnson & Son Mhp

Is Johnson & Son Mhp tap water safe to drink?

EPA monitoring detected 10 contaminants in Johnson & Son Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Johnson & Son Mhp's water?

EPA monitoring detected Nitrate, Copper, Combined Uranium, Fluoride, Nitrate-Nitrite, and others. The full list with the level and data source for each is above.

How many people does Johnson & Son Mhp serve?

Johnson & Son Mhp reports serving 102 people in North Carolina, per its EPA record.

Has Johnson & Son Mhp had any water quality violations?

The EPA has 197 violations on file for Johnson & Son Mhp, of which 13 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.