Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2003-04-01 → 2003-06-30 |
| MCL | Health-based | Resolved | 2003-04-01 → 2003-06-30 |
| MCL | Health-based | Resolved | 2003-04-01 → 2003-06-30 |
| MCL | Health-based | Resolved | 2003-04-01 → 2003-06-30 |
| MCL | Health-based | Resolved | 1994-08-01 → 1994-08-31 |
| MCL | Health-based | Resolved | 1994-08-01 → 1994-08-31 |
| MCL | Health-based | Resolved | 1994-08-01 → 1994-08-31 |
| MCL | Health-based | Resolved | 1994-08-01 → 1994-08-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 3420 µg/L 34% of the EPA limit 10000 µg/L | 20/28 | SYR4 | 2012–2019 |
| Copper | 106 µg/L 8.2% of the EPA limit 1300 µg/L | 7/15 | SYR4 | 2013–2019 |
| Trichloroethylene | 2.3 µg/L 46% of the EPA limit 5 µg/L | 4/9 | SYR4 | 2012–2019 |
| Bromodichloromethane | 10 µg/L No EPA limit set | 3/5 | SYR4 | 2014–2019 |
| Chloroform | 69 µg/L No EPA limit set | 3/5 | SYR4 | 2014–2019 |
| Fluoride | 755 µg/L 19% of the EPA limit 4000 µg/L | 3/4 | SYR4 | 2014–2019 |
| TTHM | 79 µg/L 99% of the EPA limit 80 µg/L | 3/5 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 50 µg/L 83% of the EPA limit 60 µg/L | 3/5 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 15 µg/L No EPA limit set | 3/5 | SYR4 | 2014–2019 |
| 1,1-Dichloroethylene | 0.6000 µg/L 8.6% of the EPA limit 7 µg/L | 2/9 | SYR4 | 2012–2019 |
| Atrazine | 0.1300 µg/L 4.3% of the EPA limit 3 µg/L | 2/8 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 24 µg/L No EPA limit set | 2/5 | SYR4 | 2014–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 2/2 | LCR | 2025 |
| Nitrate-Nitrite | 2470 µg/L 25% of the EPA limit 10000 µg/L | 2/2 | SYR4 | 2018 |
| Dibromochloromethane | 1.1 µg/L No EPA limit set | 1/5 | SYR4 | 2014–2019 |
| Monobromoacetic Acid | 2 µg/L No EPA limit set | 1/5 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 26 µg/L No EPA limit set | 1/5 | SYR4 | 2014–2019 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Monroe`S Mhp
Is Monroe`S Mhp tap water safe to drink?
EPA monitoring detected 17 contaminants in Monroe`S Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Monroe`S Mhp's water?
EPA monitoring detected Nitrate, Copper, Trichloroethylene, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Monroe`S Mhp serve?
Monroe`S Mhp reports serving 187 people in North Carolina, per its EPA record.
Has Monroe`S Mhp had any water quality violations?
The EPA has 1771 violations on file for Monroe`S Mhp, of which 10 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.