← North Carolina

Tap water quality report

Denton, Town of

EPA monitoring tested this supplier for 78 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

78
contaminants tested
15
detected
1,710
people served
41
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Davidson

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

41
health-based violations
320
violations on file
6
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-12-31
MCL Health-based Resolved 2005-10-01 → 2005-10-31
MCL Health-based Resolved 2005-10-01 → 2005-10-31
MCL Health-based Resolved 2005-10-01 → 2005-10-31
MCL Health-based Resolved 2005-10-01 → 2005-10-31
MCL Health-based Resolved 2005-10-01 → 2005-10-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
118 µg/L 148%
of the EPA limit, in the worst sample — 80 µg/L
49/49 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
75.3 µg/L 125%
of the EPA limit, in the worst sample — 60 µg/L
49/49 SYR4 2012–2019
Bromodichloromethane
16 µg/L
No EPA limit set
42/42 SYR4 2013–2019
Chloroform
108 µg/L
No EPA limit set
42/42 SYR4 2013–2019
Dichloroacetic Acid
39 µg/L
No EPA limit set
42/42 SYR4 2013–2019
Trichloroacetic Acid
42 µg/L
No EPA limit set
42/42 SYR4 2013–2019
Copper
430 µg/L 33%
of the EPA limit 1300 µg/L
28/30 SYR4 2012–2018
Dibromochloromethane
4 µg/L
No EPA limit set
17/42 SYR4 2013–2019
Monobromoacetic Acid
13 µg/L
No EPA limit set
11/42 SYR4 2013–2019
Monochloroacetic Acid
3 µg/L
No EPA limit set
7/42 SYR4 2013–2019
Atrazine
0.6200 µg/L 21%
of the EPA limit 3 µg/L
6/9 SYR4 2012–2019
Dibromoacetic Acid
4 µg/L
No EPA limit set
6/42 SYR4 2013–2019
Lead
18 µg/L 120%
of the EPA limit, in the worst sample — 15 µg/L
5/30 SYR4 2012–2018
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
3/3 LCR 2025
Fluoride
810 µg/L 20%
of the EPA limit 4000 µg/L
1/4 SYR4 2012–2019
63 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitrateNitrate-NitriteNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
FAUNCE, JASON
Phone
336-859-3139
Email
JASON.FAUNCE@TOWNOFDENTON.COM

Frequently asked questions about Denton, Town of

Is Denton, Town of tap water safe to drink?

EPA monitoring detected 15 contaminants in Denton, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Denton, Town of's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Denton, Town of serve?

Denton, Town of reports serving 1,710 people in North Carolina, per its EPA record.

Has Denton, Town of had any water quality violations?

The EPA has 320 violations on file for Denton, Town of, of which 41 are health-based (a contaminant limit or required treatment was breached) and 6 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.