Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2017-04-07 |
| TT | Health-based | Resolved | 2017-04-07 |
| TT | Health-based | Resolved | 2017-04-07 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 24 µg/L 240% of the EPA limit, in the worst sample — 10 µg/L | 21/31 | SYR4 | 2012–2019 |
| Combined Uranium | 7 µg/L 23% of the EPA limit 30 µg/L | 18/18 | SYR4 | 2013–2018 |
| Copper | 380 µg/L 29% of the EPA limit 1300 µg/L | 15/20 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 34 pCi/L 227% of the EPA limit, in the worst sample — 15 pCi/L | 15/18 | SYR4 | 2013–2018 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2025 |
| Nitrate-Nitrite | 30 µg/L 0.3% of the EPA limit 10000 µg/L | 8/18 | SYR4 | 2012–2019 |
| Lead | 2 µg/L 13% of the EPA limit 15 µg/L | 4/20 | SYR4 | 2013–2019 |
| Fluoride | 2800 µg/L 70% of the EPA limit 4000 µg/L | 3/3 | SYR4 | 2012–2017 |
| Bromoform | 1.4 µg/L No EPA limit set | 2/4 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 0.5800 µg/L No EPA limit set | 2/2 | SYR4 | 2018–2019 |
| Selenium | 2 µg/L 4% of the EPA limit 50 µg/L | 2/2 | SYR4 | 2012–2017 |
| TTHM | 1.7 µg/L 2.1% of the EPA limit 80 µg/L | 2/4 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 0.5800 µg/L 1% of the EPA limit 60 µg/L | 2/2 | SYR4 | 2018–2019 |
| Combined Radium (-226 And -228) | 4.8 pCi/L 96% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2013 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Spring Tree Ridge
Is Spring Tree Ridge tap water safe to drink?
EPA monitoring detected 14 contaminants in Spring Tree Ridge's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Spring Tree Ridge's water?
EPA monitoring detected Arsenic, Combined Uranium, Copper, Gross Alpha, Excl. Radon And U, Lead, and others. The full list with the level and data source for each is above.
How many people does Spring Tree Ridge serve?
Spring Tree Ridge reports serving 80 people in Montana, per its EPA record.
Has Spring Tree Ridge had any water quality violations?
The EPA has 517 violations on file for Spring Tree Ridge, of which 66 are health-based (a contaminant limit or required treatment was breached) and 8 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.