Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2024-10-01 |
| MR | Monitoring | Resolved | 2024-10-01 |
| MR | Monitoring | Resolved | 2024-10-01 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-12-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-12-31 |
| MR | Monitoring | Resolved | 2024-01-01 → 2024-12-31 |
| Other | Monitoring | Resolved | 2022-10-01 |
| Other | Monitoring | Resolved | 2022-10-01 |
| MR | Monitoring | Resolved | 2022-01-01 → 2024-12-31 |
| MR | Monitoring | Resolved | 2022-01-01 → 2024-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 383.25 µg/L 29% of the EPA limit 1300 µg/L
worst single sample: 462 µg/L | 16/16 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 259 µg/L 2.6% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2027 |
| Lead | 1.88 µg/L 13% of the EPA limit 15 µg/L
worst single sample: 2.54 µg/L | 13/16 | SYR4 | 2012–2018 |
| Barium | 51.585 µg/L 2.6% of the EPA limit 2000 µg/L
worst single sample: 51.6 µg/L | 2/2 | SYR4 | 2014–2017 |
| Chloroform | 0.4975 µg/L No EPA limit set
worst single sample: 0.5000 µg/L | 2/4 | SYR4 | 2014–2018 |
| Dibromochloromethane | 0.6910 µg/L No EPA limit set
worst single sample: 0.7000 µg/L | 2/4 | SYR4 | 2014–2018 |
| Fluoride | 585.95 µg/L 15% of the EPA limit 4000 µg/L
worst single sample: 588 µg/L | 2/2 | SYR4 | 2014–2017 |
| Gross Alpha, Excl. Radon And U | 7.6186 pCi/L 51% of the EPA limit 15 pCi/L
worst single sample: 7.7 pCi/L | 2/2 | SYR4 | 2014–2018 |
| TTHM | 1.749 µg/L 2.2% of the EPA limit 80 µg/L
worst single sample: 1.79 µg/L | 2/4 | SYR4 | 2014–2018 |
| Arsenic | 1.81 µg/L 18% of the EPA limit 10 µg/L | 1/1 | SYR4 | 2014 |
| Beryllium, Total | 0.3370 µg/L 8.4% of the EPA limit 4 µg/L | 1/2 | SYR4 | 2014–2017 |
| Bromodichloromethane | 0.5900 µg/L No EPA limit set | 1/4 | SYR4 | 2014–2018 |
| Combined Radium (-226 And -228) | 0.4190 pCi/L 8.4% of the EPA limit 5 pCi/L | 1/2 | SYR4 | 2014–2018 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Galen Facility
Is Galen Facility tap water safe to drink?
EPA monitoring detected 14 contaminants in Galen Facility's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Galen Facility's water?
EPA monitoring detected Copper, Nitrate-Nitrite, Lead, Lead, Barium, and others. The full list with the level and data source for each is above.
How many people does Galen Facility serve?
Galen Facility reports serving 90 people in Montana, per its EPA record.
Has Galen Facility had any water quality violations?
The EPA has 233 violations on file for Galen Facility, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.