Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2023-12-30 |
| MON | Monitoring | Resolved | 2022-10-01 → 2022-10-31 |
| MON | Monitoring | Resolved | 2022-10-01 → 2022-10-31 |
| MON | Monitoring | Resolved | 2022-10-01 → 2022-10-31 |
| MON | Monitoring | Resolved | 2022-10-01 → 2022-10-31 |
| Other | Monitoring | Resolved | 2019-07-01 |
| MR | Monitoring | Resolved | 2008-04-01 |
| MR | Monitoring | Resolved | 2008-04-01 |
| MR | Monitoring | Archived | 2008-01-01 → 2010-12-31 |
| MR | Monitoring | Archived | 2008-01-01 → 2010-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 846 µg/L 65% of the EPA limit 1300 µg/L | 42/42 | SYR4 | 2014–2017 |
| Nitrate-Nitrite | 7900 µg/L 79% of the EPA limit 10000 µg/L | 40/40 | SYR4 | 2012–2019 |
| Lead | 7.24 µg/L 48% of the EPA limit 15 µg/L | 31/42 | SYR4 | 2014–2017 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2023 |
| Bromodichloromethane | 3.5 µg/L No EPA limit set | 9/9 | SYR4 | 2013–2019 |
| Chloroform | 2.52 µg/L No EPA limit set | 9/9 | SYR4 | 2013–2019 |
| Dibromochloromethane | 3.69 µg/L No EPA limit set | 9/9 | SYR4 | 2013–2019 |
| TTHM | 10.4 µg/L 13% of the EPA limit 80 µg/L | 7/7 | SYR4 | 2013–2019 |
| Bromoform | 0.7800 µg/L No EPA limit set | 6/9 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 2.94 µg/L No EPA limit set | 4/7 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 1.37 µg/L No EPA limit set | 3/7 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 2.98 µg/L No EPA limit set | 3/7 | SYR4 | 2013–2019 |
| Barium | 54.2 µg/L 2.7% of the EPA limit 2000 µg/L | 2/2 | SYR4 | 2014–2017 |
| Chromium | 3.01 µg/L 3% of the EPA limit 100 µg/L | 2/2 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 4.79 µg/L No EPA limit set | 2/7 | SYR4 | 2013–2019 |
| Fluoride | 130 µg/L 3.3% of the EPA limit 4000 µg/L | 1/2 | SYR4 | 2014–2017 |
82 contaminants tested, none detected
Utility contact
Frequently asked questions about Clark County Cons Pwsd 1
Is Clark County Cons Pwsd 1 tap water safe to drink?
EPA monitoring detected 16 contaminants in Clark County Cons Pwsd 1's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Clark County Cons Pwsd 1's water?
EPA monitoring detected Copper, Nitrate-Nitrite, Lead, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Clark County Cons Pwsd 1 serve?
Clark County Cons Pwsd 1 reports serving 7,140 people in Missouri, per its EPA record.
Has Clark County Cons Pwsd 1 had any water quality violations?
The EPA has 14 violations on file for Clark County Cons Pwsd 1, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.