Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2001-03-01 → 2001-03-31 |
| TT | Health-based | Resolved | 2001-03-01 → 2001-03-31 |
| TT | Health-based | Resolved | 2001-03-01 → 2001-03-31 |
| TT | Health-based | Resolved | 2001-03-01 → 2001-03-31 |
| TT | Health-based | Resolved | 1998-04-01 → 1998-04-30 |
| TT | Health-based | Resolved | 1998-04-01 → 1998-04-30 |
| TT | Health-based | Resolved | 1998-04-01 → 1998-04-30 |
| TT | Health-based | Resolved | 1998-01-01 → 1998-01-31 |
| TT | Health-based | Resolved | 1998-01-01 → 1998-01-31 |
| TT | Health-based | Resolved | 1998-01-01 → 1998-01-31 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0071 µg/L | 3/4 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chlorite | 590 µg/L 59% of the EPA limit 1000 µg/L | 289/289 | SYR4 | 2012–2019 |
| Copper | 226 µg/L 17% of the EPA limit 1300 µg/L | 68/68 | SYR4 | 2012–2019 |
| Bromodichloromethane | 10.8 µg/L No EPA limit set | 60/60 | SYR4 | 2012–2019 |
| Chloroform | 53.1 µg/L No EPA limit set | 60/60 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.85 µg/L No EPA limit set | 60/60 | SYR4 | 2012–2019 |
| TTHM | 64 µg/L 80% of the EPA limit 80 µg/L | 52/52 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 10.8 µg/L No EPA limit set | 52/52 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 26.8 µg/L No EPA limit set | 51/52 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 36.7 µg/L 61% of the EPA limit 60 µg/L | 50/52 | SYR4 | 2012–2019 |
| Lead | 0.0022 mg/L 15% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2025 |
| Lead | 8.04 µg/L 54% of the EPA limit 15 µg/L | 19/67 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1020 µg/L 10% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Barium | 61.5 µg/L 3.1% of the EPA limit 2000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 920 µg/L 23% of the EPA limit 4000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 7.98 µg/L No EPA limit set | 6/52 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 10.6 µg/L No EPA limit set | 2/52 | SYR4 | 2012–2019 |
| Atrazine | 0.7600 µg/L 25% of the EPA limit 3 µg/L | 1/32 | SYR4 | 2012–2019 |
| Chromium | 1.04 µg/L 1% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 8.76 µg/L No EPA limit set | 1/52 | SYR4 | 2012–2019 |
| Xylenes, Total | 0.6400 µg/L 0% of the EPA limit 10000 µg/L | 1/8 | SYR4 | 2012–2019 |
78 contaminants tested, none detected
Utility contact
Frequently asked questions about Macon
Is Macon tap water safe to drink?
EPA monitoring detected 21 contaminants in Macon's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Macon's water?
EPA monitoring detected Chlorite, Copper, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Macon serve?
Macon reports serving 5,489 people in Missouri, per its EPA record.
Has Macon had any water quality violations?
The EPA has 50 violations on file for Macon, of which 23 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.