Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-07-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-09-30 |
| MCL | Health-based | Resolved | 2014-06-01 → 2014-06-30 |
| MCL | Health-based | Resolved | 2014-06-01 → 2014-06-30 |
| MCL | Health-based | Resolved | 2014-04-01 → 2014-06-30 |
| MCL | Health-based | Resolved | 2014-04-01 → 2014-06-30 |
| MCL | Health-based | Resolved | 2011-12-01 → 2011-12-31 |
| MCL | Health-based | Resolved | 2011-12-01 → 2011-12-31 |
| MCL | Health-based | Resolved | 2010-07-01 → 2010-07-31 |
| MCL | Health-based | Resolved | 2010-07-01 → 2010-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 157.5 µg/L 1.6% of the EPA limit 10000 µg/L
worst single sample: 160 µg/L | 22/56 | SYR4 | 2012–2019 |
| Copper | 21.5 µg/L 1.7% of the EPA limit 1300 µg/L
worst single sample: 26 µg/L | 16/28 | SYR4 | 2012–2019 |
| Lead | 0.0030 mg/L 20% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2024 |
| Arsenic | 5.75 µg/L 57% of the EPA limit 10 µg/L
worst single sample: 7 µg/L | 6/8 | SYR4 | 2014–2017 |
| Barium | 3 µg/L 0.2% of the EPA limit 2000 µg/L | 6/8 | SYR4 | 2014–2017 |
| Bromodichloromethane | 1.432 µg/L No EPA limit set
worst single sample: 1.48 µg/L | 3/3 | SYR4 | 2015–2017 |
| Chloroform | 1.078 µg/L No EPA limit set
worst single sample: 1.11 µg/L | 3/3 | SYR4 | 2015–2017 |
| Di(2-ethylhexyl) Phthalate | 122.1 µg/L 2035% of the EPA limit, at the 95th percentile of samples — 6 µg/L
worst single sample: 130 µg/L | 3/19 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.391 µg/L No EPA limit set
worst single sample: 1.42 µg/L | 3/3 | SYR4 | 2015–2017 |
| Fluoride | 283 µg/L 7.1% of the EPA limit 4000 µg/L
worst single sample: 300 µg/L | 3/8 | SYR4 | 2014–2017 |
| TTHM | 3.901 µg/L 4.9% of the EPA limit 80 µg/L
worst single sample: 4.01 µg/L | 3/3 | SYR4 | 2015–2017 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Trail Ridge Condominiums
Is Trail Ridge Condominiums tap water safe to drink?
EPA monitoring detected 11 contaminants in Trail Ridge Condominiums's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Trail Ridge Condominiums's water?
EPA monitoring detected Nitrate, Copper, Lead, Arsenic, Barium, and others. The full list with the level and data source for each is above.
How many people does Trail Ridge Condominiums serve?
Trail Ridge Condominiums reports serving 104 people in Massachusetts, per its EPA record.
Has Trail Ridge Condominiums had any water quality violations?
The EPA has 149 violations on file for Trail Ridge Condominiums, of which 24 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.