Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 1997-12-01 → 1997-12-31 |
| MCL | Health-based | Archived | 1997-12-01 → 1997-12-31 |
| MCL | Health-based | Archived | 1992-09-01 → 1992-09-30 |
| MCL | Health-based | Archived | 1992-09-01 → 1992-09-30 |
| MCL | Health-based | Archived | 1992-09-01 → 1992-09-30 |
| Other | Monitoring | Resolved | 2023-07-01 |
| Other | Monitoring | Resolved | 2023-07-01 |
| MR | Monitoring | Resolved | 2013-08-01 → 2014-07-31 |
| MR | Monitoring | Resolved | 2013-08-01 → 2014-07-31 |
| MR | Monitoring | Resolved | 2013-08-01 → 2014-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 36 µg/L 240% of the EPA limit, in the worst sample — 15 µg/L | 21/35 | SYR4 | 2012–2018 |
| TTHM | 27 µg/L 34% of the EPA limit 80 µg/L | 15/15 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 17.6 µg/L 29% of the EPA limit 60 µg/L | 15/15 | SYR4 | 2012–2019 |
| Bromodichloromethane | 6.5 µg/L No EPA limit set | 14/15 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 10.3 µg/L No EPA limit set | 14/16 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 6.8 µg/L No EPA limit set | 14/15 | SYR4 | 2012–2019 |
| Chloroform | 18 µg/L No EPA limit set | 13/15 | SYR4 | 2012–2019 |
| Dibromochloromethane | 19 µg/L No EPA limit set | 12/15 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2024 |
| Copper | 100 µg/L 7.7% of the EPA limit 1300 µg/L | 9/35 | SYR4 | 2012–2018 |
| Dibromoacetic Acid | 1.5 µg/L No EPA limit set | 8/16 | SYR4 | 2012–2019 |
| Fluoride | 500 µg/L 13% of the EPA limit 4000 µg/L | 8/8 | SYR4 | 2012–2018 |
| Nitrate-Nitrite | 200 µg/L 2% of the EPA limit 10000 µg/L | 8/44 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 1.28 µg/L 21% of the EPA limit 6 µg/L | 3/8 | SYR4 | 2012–2018 |
| Barium | 5.6 µg/L 0.3% of the EPA limit 2000 µg/L | 1/8 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 0.7010 pCi/L 14% of the EPA limit 5 pCi/L | 1/5 | SYR4 | 2015–2018 |
| Monochloroacetic Acid | 0.8800 µg/L No EPA limit set | 1/16 | SYR4 | 2012–2019 |
65 contaminants tested, none detected
Utility contact
Frequently asked questions about Town of St Francisville Water
Is Town of St Francisville Water tap water safe to drink?
EPA monitoring detected 17 contaminants in Town of St Francisville Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Town of St Francisville Water's water?
EPA monitoring detected Lead, TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Town of St Francisville Water serve?
Town of St Francisville Water reports serving 2,304 people in Louisiana, per its EPA record.
Has Town of St Francisville Water had any water quality violations?
The EPA has 16 violations on file for Town of St Francisville Water, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.