← Louisiana

Tap water quality report

State of La Military Dept - Camp Minden

EPA monitoring tested this supplier for 80 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

80
contaminants tested
20
detected
1,001
people served
4
health-based violations
Water source
Ground water
Ownership
State government
Counties served
Webster Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
15
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
MCL Health-based Archived 1994-04-15 → 1994-05-14
MCL Health-based Archived 1994-04-15 → 1994-05-14
MCL Health-based Archived 1994-04-15 → 1994-05-14
MR Monitoring Unaddressed 2026-02-15
RPT Monitoring Resolved 2024-10-17
Other Monitoring Resolved 2006-07-01
Other Monitoring Resolved 2006-07-01
Other Monitoring Resolved 2006-07-01
Other Monitoring Resolved 2006-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
400 µg/L 31%
of the EPA limit 1300 µg/L
17/38 SYR4 2013–2019
TTHM
50.335 µg/L 63%
of the EPA limit 80 µg/L
worst single sample: 59.5 µg/L
14/14 SYR4 2013–2019
Chloroform
2.836 µg/L
No EPA limit set
worst single sample: 3.28 µg/L
13/14 SYR4 2013–2019
Lead
24 µg/L 160%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 54 µg/L
13/38 SYR4 2013–2019
Bromoform
33.975 µg/L
No EPA limit set
worst single sample: 43.2 µg/L
10/14 SYR4 2013–2019
Dibromochloromethane
12.04 µg/L
No EPA limit set
worst single sample: 13 µg/L
9/14 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
9/9 LCR 2025
Bromodichloromethane
5.2995 µg/L
No EPA limit set
worst single sample: 6.43 µg/L
8/14 SYR4 2013–2019
Fluoride
346.5 µg/L 8.7%
of the EPA limit 4000 µg/L
worst single sample: 350 µg/L
8/8 SYR4 2012–2018
Barium
150 µg/L 7.5%
of the EPA limit 2000 µg/L
6/9 SYR4 2012–2018
Dibromoacetic Acid
5.92 µg/L
No EPA limit set
worst single sample: 6.96 µg/L
6/14 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
6.17 µg/L 10%
of the EPA limit 60 µg/L
worst single sample: 6.96 µg/L
6/14 SYR4 2013–2019
Di(2-ethylhexyl) Phthalate
0.8370 µg/L 14%
of the EPA limit 6 µg/L
worst single sample: 0.8400 µg/L
4/9 SYR4 2012–2018
Dichloroacetic Acid
0.9675 µg/L
No EPA limit set
worst single sample: 0.9900 µg/L
4/14 SYR4 2013–2019
Gross Beta Particle Activity
1.6755 pCi/L
No EPA limit set
worst single sample: 1.68 pCi/L
4/9 SYR4 2012–2018
Nitrate-Nitrite
36 µg/L 0.4%
of the EPA limit 10000 µg/L
4/44 SYR4 2012–2019
Combined Radium (-226 And -228)
1.04415 pCi/L 21%
of the EPA limit 5 pCi/L
worst single sample: 1.06 pCi/L
2/6 SYR4 2015–2018
Benzene
0.2700 µg/L 5.4%
of the EPA limit 5 µg/L
1/12 SYR4 2012–2018
Toluene
3.2 µg/L 0.3%
of the EPA limit 1000 µg/L
1/12 SYR4 2012–2018
Xylenes, Total
3.2 µg/L 0%
of the EPA limit 10000 µg/L
1/12 SYR4 2012–2018
60 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PRYMEK, MARC
Phone
318-299-4183
Email
marc.e.prymek.nfg@army.mil

Frequently asked questions about State of La Military Dept - Camp Minden

Is State of La Military Dept - Camp Minden tap water safe to drink?

EPA monitoring detected 20 contaminants in State of La Military Dept - Camp Minden's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in State of La Military Dept - Camp Minden's water?

EPA monitoring detected Copper, TTHM, Chloroform, Lead, Bromoform, and others. The full list with the level and data source for each is above.

How many people does State of La Military Dept - Camp Minden serve?

State of La Military Dept - Camp Minden reports serving 1,001 people in Louisiana, per its EPA record.

Has State of La Military Dept - Camp Minden had any water quality violations?

The EPA has 15 violations on file for State of La Military Dept - Camp Minden, of which 4 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.