Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromoform | 235.45 µg/L No EPA limit set
worst single sample: 271 µg/L | 54/56 | SYR4 | 2012–2019 |
| Dibromochloromethane | 93.345 µg/L No EPA limit set
worst single sample: 110 µg/L | 54/56 | SYR4 | 2012–2019 |
| TTHM | 340.09 µg/L 425% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 401.4 µg/L | 54/56 | SYR4 | 2012–2019 |
| Bromodichloromethane | 22.56 µg/L No EPA limit set
worst single sample: 26.5 µg/L | 53/56 | SYR4 | 2012–2019 |
| Chloroform | 8.14 µg/L No EPA limit set
worst single sample: 9.9 µg/L | 53/56 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 59.655 µg/L 99% of the EPA limit 60 µg/L
worst single sample: 75 µg/L | 52/56 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 47.45 µg/L No EPA limit set
worst single sample: 58.1 µg/L | 51/56 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 4.7 µg/L No EPA limit set
worst single sample: 5.1 µg/L | 35/56 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 10.835 µg/L No EPA limit set
worst single sample: 16.7 µg/L | 30/56 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 6.44 µg/L No EPA limit set
worst single sample: 7.9 µg/L | 29/56 | SYR4 | 2012–2019 |
| Lead | 2.9 µg/L 19% of the EPA limit 15 µg/L
worst single sample: 4.6 µg/L | 23/36 | SYR4 | 2013–2019 |
| Copper | 500 µg/L 38% of the EPA limit 1300 µg/L | 13/36 | SYR4 | 2013–2019 |
| Fluoride | 500 µg/L 13% of the EPA limit 4000 µg/L | 9/9 | SYR4 | 2012–2018 |
| Lead | 0.0024 mg/L 16% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2025 |
| Barium | 22.25 µg/L 1.1% of the EPA limit 2000 µg/L
worst single sample: 23 µg/L | 6/9 | SYR4 | 2012–2018 |
| Di(2-ethylhexyl) Phthalate | 0.7935 µg/L 13% of the EPA limit 6 µg/L
worst single sample: 0.8400 µg/L | 4/9 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 5.61 µg/L No EPA limit set
worst single sample: 5.7 µg/L | 4/56 | SYR4 | 2012–2019 |
| Arsenic | 1 µg/L 10% of the EPA limit 10 µg/L | 3/9 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 1.4837 pCi/L 30% of the EPA limit 5 pCi/L
worst single sample: 1.52 pCi/L | 2/3 | SYR4 | 2018 |
| Nitrate-Nitrite | 44 µg/L 0.4% of the EPA limit 10000 µg/L | 2/48 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 1.42 pCi/L No EPA limit set | 1/9 | SYR4 | 2012–2018 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Linville-Haile Water
Is Linville-Haile Water tap water safe to drink?
EPA monitoring detected 21 contaminants in Linville-Haile Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Linville-Haile Water's water?
EPA monitoring detected Bromoform, Dibromochloromethane, TTHM, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Linville-Haile Water serve?
Linville-Haile Water reports serving 1,635 people in Louisiana, per its EPA record.
Has Linville-Haile Water had any water quality violations?
The EPA has 672 violations on file for Linville-Haile Water, of which 564 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.