Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 52.4 µg/L No EPA limit set | 68/71 | SYR4 | 2012–2019 |
| Bromoform | 19.2 µg/L No EPA limit set | 68/71 | SYR4 | 2012–2019 |
| Chloroform | 34.1 µg/L No EPA limit set | 68/71 | SYR4 | 2012–2019 |
| Dibromochloromethane | 74.4 µg/L No EPA limit set | 68/71 | SYR4 | 2012–2019 |
| TTHM | 162.2 µg/L 203% of the EPA limit, in the worst sample — 80 µg/L | 68/71 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 38 µg/L 63% of the EPA limit 60 µg/L | 38/71 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 19.7 µg/L No EPA limit set | 37/71 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 11.2 µg/L No EPA limit set | 30/71 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 8.04 µg/L No EPA limit set | 29/71 | SYR4 | 2012–2019 |
| Fluoride | 310 µg/L 7.8% of the EPA limit 4000 µg/L | 12/12 | SYR4 | 2013–2019 |
| Copper | 200 µg/L 15% of the EPA limit 1300 µg/L | 10/38 | SYR4 | 2012–2019 |
| Lead | 0.0030 mg/L 20% of the EPA limit 0.0150 mg/L | 8/8 | LCR | 2024 |
| Monobromoacetic Acid | 6.61 µg/L No EPA limit set | 8/71 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.98 pCi/L 40% of the EPA limit 5 pCi/L | 6/8 | SYR4 | 2016–2019 |
| Nitrate-Nitrite | 32 µg/L 0.3% of the EPA limit 10000 µg/L | 6/44 | SYR4 | 2012–2019 |
| Barium | 5.7 µg/L 0.3% of the EPA limit 2000 µg/L | 5/12 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 1.7 µg/L No EPA limit set | 5/71 | SYR4 | 2012–2019 |
| Lead | 1 µg/L 6.7% of the EPA limit 15 µg/L | 4/38 | SYR4 | 2012–2019 |
| Arsenic | 0.8900 µg/L 8.9% of the EPA limit 10 µg/L | 3/12 | SYR4 | 2013–2019 |
| Cyanide | 4.1 µg/L 2.1% of the EPA limit 200 µg/L | 2/12 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Phthalate | 0.5300 µg/L 8.8% of the EPA limit 6 µg/L | 1/12 | SYR4 | 2013–2019 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Hico Water
Is Hico Water tap water safe to drink?
EPA monitoring detected 21 contaminants in Hico Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Hico Water's water?
EPA monitoring detected Bromodichloromethane, Bromoform, Chloroform, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does Hico Water serve?
Hico Water reports serving 1,530 people in Louisiana, per its EPA record.
Has Hico Water had any water quality violations?
The EPA has 427 violations on file for Hico Water, of which 317 are health-based (a contaminant limit or required treatment was breached) and 10 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.