Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2025-05-01 |
| TT | Health-based | Unaddressed | 2025-05-01 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2013-06-01 → 2013-06-30 |
| MCL | Health-based | Resolved | 2003-09-01 → 2003-09-30 |
| MCL | Health-based | Resolved | 2003-09-01 → 2003-09-30 |
| MCL | Health-based | Resolved | 2003-09-01 → 2003-09-30 |
| MCL | Health-based | Resolved | 2003-09-01 → 2003-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 5.9 µg/L 39% of the EPA limit 15 µg/L
worst single sample: 18 µg/L | 23/36 | SYR4 | 2013–2019 |
| Copper | 1315 µg/L 101% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 1600 µg/L | 20/36 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 180 µg/L 1.8% of the EPA limit 10000 µg/L | 16/44 | SYR4 | 2012–2019 |
| Fluoride | 196.5 µg/L 4.9% of the EPA limit 4000 µg/L
worst single sample: 200 µg/L | 8/9 | SYR4 | 2013–2019 |
| Lead | 0.0050 mg/L 33% of the EPA limit 0.0150 mg/L | 8/8 | LCR | 2025 |
| Barium | 35.75 µg/L 1.8% of the EPA limit 2000 µg/L
worst single sample: 36 µg/L | 6/9 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 2.38 µg/L 4% of the EPA limit 60 µg/L
worst single sample: 2.69 µg/L | 6/14 | SYR4 | 2013–2019 |
| Chloroform | 1.442 µg/L No EPA limit set
worst single sample: 1.47 µg/L | 5/14 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 0.9360 µg/L No EPA limit set
worst single sample: 0.9700 µg/L | 5/14 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 3.162 pCi/L No EPA limit set
worst single sample: 3.24 pCi/L | 5/10 | SYR4 | 2013–2019 |
| TTHM | 2.974 µg/L 3.7% of the EPA limit 80 µg/L
worst single sample: 3.35 µg/L | 5/14 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 0.9370 µg/L No EPA limit set
worst single sample: 0.9700 µg/L | 4/14 | SYR4 | 2013–2019 |
| Bromodichloromethane | 0.9775 µg/L No EPA limit set
worst single sample: 1.01 µg/L | 2/14 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 0.9122 pCi/L 18% of the EPA limit 5 pCi/L
worst single sample: 0.9150 pCi/L | 2/6 | SYR4 | 2016–2019 |
| Di(2-ethylhexyl) Phthalate | 0.6360 µg/L 11% of the EPA limit 6 µg/L
worst single sample: 0.6400 µg/L | 2/9 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 0.9170 µg/L No EPA limit set
worst single sample: 0.9400 µg/L | 2/14 | SYR4 | 2013–2019 |
| 1,2-DIBROMO-3-CHLOROPROPANE | 8.945 µg/L 4473% of the EPA limit, at the 95th percentile of samples — 0.2000 µg/L | 1/10 | SYR4 | 2013–2019 |
| Dalapon | 2.24 µg/L 1.1% of the EPA limit 200 µg/L | 1/9 | SYR4 | 2013–2019 |
| Dibromochloromethane | 1.01 µg/L No EPA limit set | 1/14 | SYR4 | 2013–2019 |
| Hexachlorobenzene | 0.0740 µg/L 7.4% of the EPA limit 1 µg/L | 1/10 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 0.4000 µg/L No EPA limit set | 1/14 | SYR4 | 2013–2019 |
61 contaminants tested, none detected
Utility contact
Frequently asked questions about Fellowship Water
Is Fellowship Water tap water safe to drink?
EPA monitoring detected 21 contaminants in Fellowship Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Fellowship Water's water?
EPA monitoring detected Lead, Copper, Nitrate-Nitrite, Fluoride, Lead, and others. The full list with the level and data source for each is above.
How many people does Fellowship Water serve?
Fellowship Water reports serving 795 people in Louisiana, per its EPA record.
Has Fellowship Water had any water quality violations?
The EPA has 28 violations on file for Fellowship Water, of which 17 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.