Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2014-12-01 |
| TT | Health-based | Resolved | 2014-12-01 |
| TT | Health-based | Resolved | 2014-12-01 |
| TT | Health-based | Resolved | 2014-12-01 |
| TT | Health-based | Resolved | 2012-01-01 |
| TT | Health-based | Resolved | 2012-01-01 |
| MCL | Health-based | Archived | 2008-09-01 → 2008-09-30 |
| MCL | Health-based | Archived | 2004-10-01 → 2004-10-31 |
| MCL | Health-based | Archived | 2004-10-01 → 2004-10-31 |
| MCL | Health-based | Archived | 2004-10-01 → 2004-10-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate-Nitrite | 260 µg/L 2.6% of the EPA limit 10000 µg/L | 14/22 | SYR4 | 2012–2019 |
| Lead | 0.0060 mg/L 40% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2023 |
| Copper | 300 µg/L 23% of the EPA limit 1300 µg/L | 9/25 | SYR4 | 2014–2017 |
| Chloroform | 1.4 µg/L No EPA limit set | 7/14 | SYR4 | 2013–2019 |
| TTHM | 3.3 µg/L 4.1% of the EPA limit 80 µg/L | 7/14 | SYR4 | 2013–2019 |
| Lead | 10 µg/L 67% of the EPA limit 15 µg/L | 6/25 | SYR4 | 2014–2017 |
| Total Haloacetic Acids (HAA5) | 3.3 µg/L 5.5% of the EPA limit 60 µg/L | 6/14 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 2.4 µg/L No EPA limit set | 5/14 | SYR4 | 2013–2019 |
| Barium | 33 µg/L 1.7% of the EPA limit 2000 µg/L | 4/6 | SYR4 | 2012–2017 |
| Bromodichloromethane | 1.1 µg/L No EPA limit set | 4/14 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 0.6100 µg/L No EPA limit set | 4/14 | SYR4 | 2013–2019 |
| Fluoride | 140 µg/L 3.5% of the EPA limit 4000 µg/L | 4/6 | SYR4 | 2012–2017 |
| Dibromochloromethane | 0.8700 µg/L No EPA limit set | 3/14 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Phthalate | 0.5900 µg/L 9.8% of the EPA limit 6 µg/L | 2/4 | SYR4 | 2012–2016 |
| Monochloroacetic Acid | 1.1 µg/L No EPA limit set | 2/14 | SYR4 | 2013–2019 |
| Arsenic | 1 µg/L 10% of the EPA limit 10 µg/L | 1/6 | SYR4 | 2012–2017 |
94 contaminants tested, none detected
Utility contact
Frequently asked questions about Summerville Water
Is Summerville Water tap water safe to drink?
EPA monitoring detected 16 contaminants in Summerville Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Summerville Water's water?
EPA monitoring detected Nitrate-Nitrite, Lead, Copper, Chloroform, TTHM, and others. The full list with the level and data source for each is above.
How many people does Summerville Water serve?
Summerville Water reports serving 1,425 people in Louisiana, per its EPA record.
Has Summerville Water had any water quality violations?
The EPA has 18 violations on file for Summerville Water, of which 10 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.