← Louisiana

Tap water quality report

Lpwd North Production Facility

EPA monitoring tested this supplier for 110 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
23
detected
4,122
people served
4
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Lafayette Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
6
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2012-03-01 → 2012-03-31
MCL Health-based Resolved 2012-03-01 → 2012-03-31
MCL Health-based Resolved 2012-03-01 → 2012-03-31
MCL Health-based Resolved 2012-03-01 → 2012-03-31
Other Monitoring Resolved 2025-07-01
Other Monitoring Resolved 2025-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1100 µg/L 85%
of the EPA limit 1300 µg/L
30/47 SYR4 2014–2019
Nitrate-Nitrite
1000 µg/L 10%
of the EPA limit 10000 µg/L
20/34 SYR4 2012–2019
Dibromochloromethane
2.5 µg/L
No EPA limit set
13/15 SYR4 2012–2019
TTHM
7.9 µg/L 9.9%
of the EPA limit 80 µg/L
13/15 SYR4 2012–2019
Arsenic
7 µg/L 70%
of the EPA limit 10 µg/L
10/11 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
8 µg/L 13%
of the EPA limit 60 µg/L
10/14 SYR4 2013–2019
Fluoride
340 µg/L 8.5%
of the EPA limit 4000 µg/L
9/9 SYR4 2012–2019
Bromoform
1.5 µg/L
No EPA limit set
8/15 SYR4 2012–2019
Dibromoacetic Acid
1.5 µg/L
No EPA limit set
7/14 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
6/6 LCR 2023
Lead
3 µg/L 20%
of the EPA limit 15 µg/L
6/47 SYR4 2014–2019
Bromodichloromethane
2.7 µg/L
No EPA limit set
5/15 SYR4 2012–2019
Chloroform
2.7 µg/L
No EPA limit set
3/15 SYR4 2012–2019
Chromium
10 µg/L 10%
of the EPA limit 100 µg/L
3/9 SYR4 2012–2019
Combined Radium (-226 And -228)
1.08 pCi/L 22%
of the EPA limit 5 pCi/L
3/5 SYR4 2015–2019
Dichloroacetic Acid
8 µg/L
No EPA limit set
3/14 SYR4 2013–2019
Gross Beta Particle Activity
2.99 pCi/L
No EPA limit set
3/7 SYR4 2012–2019
Barium
83 µg/L 4.2%
of the EPA limit 2000 µg/L
2/9 SYR4 2012–2019
Monochloroacetic Acid
3.6 µg/L
No EPA limit set
2/14 SYR4 2013–2019
Lithium
13.4 µg/L
No EPA limit set
2/2 UCMR-5 2024
Dalapon
2.1 µg/L 1.1%
of the EPA limit 200 µg/L
1/7 SYR4 2012–2019
Selenium
0.5100 µg/L 1%
of the EPA limit 50 µg/L
1/9 SYR4 2012–2019
Trichloroacetic Acid
1.7 µg/L
No EPA limit set
1/14 SYR4 2013–2019
87 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
GUILLORY, BYRON
Phone
337-896-8683
Email
bguillory@lpwdn.com

Frequently asked questions about Lpwd North Production Facility

Is Lpwd North Production Facility tap water safe to drink?

EPA monitoring detected 23 contaminants in Lpwd North Production Facility's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Lpwd North Production Facility's water?

EPA monitoring detected Copper, Nitrate-Nitrite, Dibromochloromethane, TTHM, Arsenic, and others. The full list with the level and data source for each is above.

How many people does Lpwd North Production Facility serve?

Lpwd North Production Facility reports serving 4,122 people in Louisiana, per its EPA record.

Has Lpwd North Production Facility had any water quality violations?

The EPA has 6 violations on file for Lpwd North Production Facility, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.