← Louisiana

Tap water quality report

Calcasieu Parish Ww District 7

EPA monitoring tested this supplier for 110 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

110
contaminants tested
17
detected
4,791
people served
13
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Calcasieu Parish

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

13
health-based violations
13
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2009-06-01 → 2009-06-30
MCL Health-based Resolved 2009-06-01 → 2009-06-30
MCL Health-based Resolved 2009-06-01 → 2009-06-30
MCL Health-based Resolved 2007-10-01 → 2007-10-31
MCL Health-based Resolved 2007-10-01 → 2007-10-31
MCL Health-based Resolved 2007-10-01 → 2007-10-31
MCL Health-based Resolved 2007-10-01 → 2007-10-31
MCL Health-based Archived 2002-05-15 → 2002-06-14
MCL Health-based Archived 2002-05-15 → 2002-06-14
MCL Health-based Archived 2002-05-15 → 2002-06-14

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
300 µg/L 23%
of the EPA limit 1300 µg/L
27/43 SYR4 2014–2017
Bromodichloromethane
15.577 µg/L
No EPA limit set
worst single sample: 18.09 µg/L
15/15 SYR4 2013–2019
Chloroform
14.357 µg/L
No EPA limit set
worst single sample: 15.19 µg/L
15/15 SYR4 2013–2019
Dibromoacetic Acid
3.66 µg/L
No EPA limit set
worst single sample: 3.8 µg/L
15/15 SYR4 2013–2019
Dibromochloromethane
12.854 µg/L
No EPA limit set
worst single sample: 13.68 µg/L
15/15 SYR4 2013–2019
Dichloroacetic Acid
7.16 µg/L
No EPA limit set
worst single sample: 8 µg/L
15/15 SYR4 2013–2019
TTHM
44.82 µg/L 56%
of the EPA limit 80 µg/L
worst single sample: 50 µg/L
15/15 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
15.89 µg/L 26%
of the EPA limit 60 µg/L
worst single sample: 18.2 µg/L
15/15 SYR4 2013–2019
Trichloroacetic Acid
5.19 µg/L
No EPA limit set
worst single sample: 6.8 µg/L
15/15 SYR4 2013–2019
Bromoform
3.11 µg/L
No EPA limit set
worst single sample: 3.18 µg/L
11/15 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
11/11 LCR 2024
Lead
1.7 µg/L 11%
of the EPA limit 15 µg/L
worst single sample: 2 µg/L
7/43 SYR4 2014–2017
Fluoride
400 µg/L 10%
of the EPA limit 4000 µg/L
6/6 SYR4 2014–2017
Arsenic
2.85 µg/L 29%
of the EPA limit 10 µg/L
worst single sample: 3 µg/L
4/6 SYR4 2014–2017
Monochloroacetic Acid
4.895 µg/L
No EPA limit set
worst single sample: 5 µg/L
4/15 SYR4 2013–2019
Di(2-ethylhexyl) Phthalate
1.155 µg/L 19%
of the EPA limit 6 µg/L
worst single sample: 1.17 µg/L
3/6 SYR4 2014–2017
Gross Beta Particle Activity
1.5445 pCi/L
No EPA limit set
worst single sample: 1.55 pCi/L
2/6 SYR4 2014–2017
93 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)Combined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateGross Alpha, Excl. Radon And UHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaNitrate-NitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TAROU, IVAN
Phone
337-786-5578
Email
WD7CAL@YAHOO.COM

Frequently asked questions about Calcasieu Parish Ww District 7

Is Calcasieu Parish Ww District 7 tap water safe to drink?

EPA monitoring detected 17 contaminants in Calcasieu Parish Ww District 7's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Calcasieu Parish Ww District 7's water?

EPA monitoring detected Copper, Bromodichloromethane, Chloroform, Dibromoacetic Acid, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Calcasieu Parish Ww District 7 serve?

Calcasieu Parish Ww District 7 reports serving 4,791 people in Louisiana, per its EPA record.

Has Calcasieu Parish Ww District 7 had any water quality violations?

The EPA has 13 violations on file for Calcasieu Parish Ww District 7, of which 13 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.