← Kentucky

Tap water quality report

North Hopkins Water District

EPA monitoring tested this supplier for 35 contaminants and detected 6. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

35
contaminants tested
6
detected
3,725
people served
74
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Hopkins

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

74
health-based violations
113
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-04-01 → 2017-06-30
MCL Health-based Resolved 2017-01-01 → 2017-03-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0063 µg/L 1/8 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
156 µg/L 12%
of the EPA limit 1300 µg/L
55/60 SYR4 2012–2018
TTHM
175 µg/L 219%
of the EPA limit, in the worst sample — 80 µg/L
53/53 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
94 µg/L 157%
of the EPA limit, in the worst sample — 60 µg/L
53/53 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2023
Lead
5 µg/L 33%
of the EPA limit 15 µg/L
2/60 SYR4 2012–2018
29 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaNetfosaaNfdhaNmefosaaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
OAKLEY, STEVE
Phone
270-825-1623
Email
northhopkinswd@yahoo.com

Frequently asked questions about North Hopkins Water District

Is North Hopkins Water District tap water safe to drink?

EPA monitoring detected 6 contaminants in North Hopkins Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in North Hopkins Water District's water?

EPA monitoring detected Copper, TTHM, Total Haloacetic Acids (HAA5), Lead, Lead, and others. The full list with the level and data source for each is above.

How many people does North Hopkins Water District serve?

North Hopkins Water District reports serving 3,725 people in Kentucky, per its EPA record.

Has North Hopkins Water District had any water quality violations?

The EPA has 113 violations on file for North Hopkins Water District, of which 74 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.