← Kansas

Tap water quality report

Wilson Co Rwd 2

EPA monitoring tested this supplier for 14 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
14
detected
194
people served
16
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Wilson

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

16
health-based violations
261
violations on file
10
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2018-01-01 → 2018-03-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-10-01 → 2017-12-31
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
41 µg/L 3.2%
of the EPA limit 1300 µg/L
worst single sample: 68 µg/L
16/16 SYR4 2013–2019
Bromodichloromethane
26.6 µg/L
No EPA limit set
worst single sample: 28 µg/L
15/15 SYR4 2015–2019
Chloroform
70.8 µg/L
No EPA limit set
worst single sample: 75 µg/L
15/15 SYR4 2015–2019
Dibromoacetic Acid
3.86 µg/L
No EPA limit set
worst single sample: 4 µg/L
15/15 SYR4 2015–2019
Dibromochloromethane
13.3 µg/L
No EPA limit set
worst single sample: 14 µg/L
15/15 SYR4 2015–2019
Dichloroacetic Acid
45.1 µg/L
No EPA limit set
worst single sample: 71 µg/L
15/15 SYR4 2015–2019
TTHM
93.7 µg/L 117%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 100 µg/L
15/15 SYR4 2015–2019
Total Haloacetic Acids (HAA5)
81.7 µg/L 136%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 130 µg/L
15/15 SYR4 2015–2019
Trichloroacetic Acid
31.8 µg/L
No EPA limit set
worst single sample: 57 µg/L
15/15 SYR4 2015–2019
Bromoform
2.31 µg/L
No EPA limit set
worst single sample: 2.4 µg/L
10/15 SYR4 2015–2019
Monochloroacetic Acid
3.32 µg/L
No EPA limit set
worst single sample: 3.4 µg/L
9/15 SYR4 2015–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
7/7 LCR 2025
Monobromoacetic Acid
1.7 µg/L
No EPA limit set
worst single sample: 1.8 µg/L
5/15 SYR4 2015–2019
Lead
2.8 µg/L 19%
of the EPA limit 15 µg/L
1/16 SYR4 2013–2019

Utility contact

Contact
HUFFORD, LUKE
Phone
620-330-5283
Email
LHuffordwater23@gmail.com

Frequently asked questions about Wilson Co Rwd 2

Is Wilson Co Rwd 2 tap water safe to drink?

EPA monitoring detected 14 contaminants in Wilson Co Rwd 2's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Wilson Co Rwd 2's water?

EPA monitoring detected Copper, Bromodichloromethane, Chloroform, Dibromoacetic Acid, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Wilson Co Rwd 2 serve?

Wilson Co Rwd 2 reports serving 194 people in Kansas, per its EPA record.

Has Wilson Co Rwd 2 had any water quality violations?

The EPA has 261 violations on file for Wilson Co Rwd 2, of which 16 are health-based (a contaminant limit or required treatment was breached) and 10 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.