← Kansas

Tap water quality report

G and P Properties Llc

EPA monitoring tested this supplier for 52 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

52
contaminants tested
20
detected
50
people served
24
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Finney

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

24
health-based violations
109
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2021-05-26
TT Health-based Resolved 2021-05-26
TT Health-based Resolved 2021-05-26
TT Health-based Resolved 2021-05-26
MCL Health-based Resolved 1999-05-01 → 1999-05-31
MCL Health-based Resolved 1999-05-01 → 1999-05-31
MCL Health-based Resolved 1999-05-01 → 1999-05-31
MCL Health-based Resolved 1999-05-01 → 1999-05-31
MCL Health-based Resolved 1999-05-01 → 1999-05-31
MCL Health-based Resolved 1999-05-01 → 1999-05-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
4300 µg/L 43%
of the EPA limit 10000 µg/L
22/22 SYR4 2012–2019
Copper
63 µg/L 4.8%
of the EPA limit 1300 µg/L
17/17 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
8/8 LCR 2025
Combined Uranium
18.4 µg/L 61%
of the EPA limit 30 µg/L
7/7 SYR4 2012–2014
Gross Alpha, Excl. Radon And U
14.3 pCi/L 95%
of the EPA limit 15 pCi/L
5/7 SYR4 2012–2014
Bromoform
3.7 µg/L
No EPA limit set
4/4 SYR4 2013–2019
Dibromoacetic Acid
2.4 µg/L
No EPA limit set
4/4 SYR4 2013–2019
Arsenic
5.7 µg/L 57%
of the EPA limit 10 µg/L
3/3 SYR4 2013–2019
Barium
15 µg/L 0.8%
of the EPA limit 2000 µg/L
3/3 SYR4 2013–2019
Fluoride
410 µg/L 10%
of the EPA limit 4000 µg/L
3/3 SYR4 2013–2019
Selenium
16 µg/L 32%
of the EPA limit 50 µg/L
3/3 SYR4 2013–2019
TTHM
6.1 µg/L 7.6%
of the EPA limit 80 µg/L
3/4 SYR4 2013–2019
Chloroform
1.7 µg/L
No EPA limit set
2/4 SYR4 2013–2019
Chromium
2 µg/L 2%
of the EPA limit 100 µg/L
2/3 SYR4 2013–2019
Combined Radium (-226 And -228)
1.3 pCi/L 26%
of the EPA limit 5 pCi/L
2/2 SYR4 2014–2017
Trichloroacetic Acid
1.6 µg/L
No EPA limit set
2/4 SYR4 2013–2019
Atrazine
0.4300 µg/L 14%
of the EPA limit 3 µg/L
1/3 SYR4 2013–2019
Dibromochloromethane
0.9200 µg/L
No EPA limit set
1/4 SYR4 2013–2019
Dichloroacetic Acid
0.7300 µg/L
No EPA limit set
1/4 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
3 µg/L 5%
of the EPA limit 60 µg/L
1/4 SYR4 2013–2019
32 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalBenzeneBeryllium, TotalBromodichloromethaneChlorobenzeneCadmiumCarbon TetrachlorideDichloromethaneEthylene DibromideEthylbenzeneLeadMercuryMonobromoacetic AcidMonochloroacetic AcidStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PRIETO, SUZANA
Phone
620-640-3135
Email
g8ppropertiesllc@gmail.com

Frequently asked questions about G and P Properties Llc

Is G and P Properties Llc tap water safe to drink?

EPA monitoring detected 20 contaminants in G and P Properties Llc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in G and P Properties Llc's water?

EPA monitoring detected Nitrate, Copper, Lead, Combined Uranium, Gross Alpha, Excl. Radon And U, and others. The full list with the level and data source for each is above.

How many people does G and P Properties Llc serve?

G and P Properties Llc reports serving 50 people in Kansas, per its EPA record.

Has G and P Properties Llc had any water quality violations?

The EPA has 109 violations on file for G and P Properties Llc, of which 24 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.