Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2004-03-01 → 2004-03-31 |
| MCL | Health-based | Resolved | 2004-03-01 → 2004-03-31 |
| MCL | Health-based | Resolved | 2004-03-01 → 2004-03-31 |
| MCL | Health-based | Resolved | 2004-03-01 → 2004-03-31 |
| Other | Monitoring | Resolved | 2016-05-14 |
| Other | Monitoring | Resolved | 2016-05-14 |
| MR | Monitoring | Resolved | 2014-10-01 → 2014-12-31 |
| MR | Monitoring | Resolved | 2014-10-01 → 2014-12-31 |
| MR | Monitoring | Resolved | 2014-10-01 → 2014-12-31 |
| MR | Monitoring | Resolved | 2014-10-01 → 2014-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 47.3 µg/L No EPA limit set
worst single sample: 66 µg/L | 18/18 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 71.55 µg/L No EPA limit set
worst single sample: 86 µg/L | 18/18 | SYR4 | 2014–2019 |
| TTHM | 72.05 µg/L 90% of the EPA limit 80 µg/L
worst single sample: 78 µg/L | 18/18 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 13.4 µg/L No EPA limit set
worst single sample: 15 µg/L | 17/18 | SYR4 | 2014–2019 |
| Copper | 200 µg/L 15% of the EPA limit 1300 µg/L
worst single sample: 410 µg/L | 16/16 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 80.5 µg/L 134% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 88 µg/L | 16/18 | SYR4 | 2014–2019 |
| Bromodichloromethane | 19.1 µg/L No EPA limit set
worst single sample: 24 µg/L | 15/18 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 10.45 µg/L No EPA limit set
worst single sample: 11 µg/L | 12/18 | SYR4 | 2014–2019 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2025 |
| Dibromoacetic Acid | 3 µg/L No EPA limit set | 6/18 | SYR4 | 2014–2019 |
| Monobromoacetic Acid | 1.13 µg/L No EPA limit set
worst single sample: 1.2 µg/L | 6/18 | SYR4 | 2014–2019 |
| Dibromochloromethane | 11.8 µg/L No EPA limit set
worst single sample: 12 µg/L | 5/18 | SYR4 | 2014–2019 |
| Lead | 4.84 µg/L 32% of the EPA limit 15 µg/L
worst single sample: 4.9 µg/L | 5/16 | SYR4 | 2013–2019 |
| Bromoform | 1.2 µg/L No EPA limit set | 4/18 | SYR4 | 2014–2019 |
Utility contact
Frequently asked questions about Allen Co Rwd 13
Is Allen Co Rwd 13 tap water safe to drink?
EPA monitoring detected 14 contaminants in Allen Co Rwd 13's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Allen Co Rwd 13's water?
EPA monitoring detected Chloroform, Dichloroacetic Acid, TTHM, Trichloroacetic Acid, Copper, and others. The full list with the level and data source for each is above.
How many people does Allen Co Rwd 13 serve?
Allen Co Rwd 13 reports serving 100 people in Kansas, per its EPA record.
Has Allen Co Rwd 13 had any water quality violations?
The EPA has 20 violations on file for Allen Co Rwd 13, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.