Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2011-05-01 → 2011-05-31 |
| MCL | Health-based | Resolved | 2011-05-01 → 2011-05-31 |
| MCL | Health-based | Resolved | 2011-05-01 → 2011-05-31 |
| MCL | Health-based | Resolved | 2011-05-01 → 2011-05-31 |
| Other | Monitoring | Resolved | 2011-07-16 |
| Other | Monitoring | Resolved | 2011-07-16 |
| MR | Monitoring | Resolved | 2011-06-01 → 2011-06-30 |
| MR | Monitoring | Resolved | 2011-06-01 → 2011-06-30 |
| MR | Monitoring | Resolved | 2011-06-01 → 2011-06-30 |
| MR | Monitoring | Resolved | 2011-06-01 → 2011-06-30 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0098 µg/L | 4/4 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 24.5 µg/L No EPA limit set | 128/128 | SYR4 | 2012–2019 |
| Chloroform | 66.1 µg/L No EPA limit set | 128/128 | SYR4 | 2012–2019 |
| Dibromochloromethane | 15.9 µg/L No EPA limit set | 128/128 | SYR4 | 2012–2019 |
| TTHM | 97.4 µg/L 122% of the EPA limit, in the worst sample — 80 µg/L | 128/128 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 28.6 µg/L 48% of the EPA limit 60 µg/L | 128/128 | SYR4 | 2012–2019 |
| Bromoform | 4.4 µg/L No EPA limit set | 126/128 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 5.9 µg/L No EPA limit set | 126/128 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 17.5 µg/L No EPA limit set | 124/128 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 8.9 µg/L No EPA limit set | 112/128 | SYR4 | 2012–2019 |
| Nitrate | 1900 µg/L 19% of the EPA limit 10000 µg/L | 22/28 | SYR4 | 2012–2019 |
| Copper | 19 µg/L 1.5% of the EPA limit 1300 µg/L | 21/60 | SYR4 | 2014–2017 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2025 |
| Barium | 140 µg/L 7% of the EPA limit 2000 µg/L | 14/14 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 4.55 µg/L No EPA limit set | 14/128 | SYR4 | 2012–2019 |
| Fluoride | 915 µg/L 23% of the EPA limit 4000 µg/L | 9/14 | SYR4 | 2012–2019 |
| Arsenic | 9.4 µg/L 94% of the EPA limit 10 µg/L | 8/14 | SYR4 | 2012–2019 |
| Lead | 2.3 µg/L 15% of the EPA limit 15 µg/L | 6/60 | SYR4 | 2014–2017 |
| Nitrate-Nitrite | 1400 µg/L 14% of the EPA limit 10000 µg/L | 6/9 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.778 pCi/L 36% of the EPA limit 5 pCi/L | 3/3 | SYR4 | 2014–2017 |
| Monochloroacetic Acid | 3.21 µg/L No EPA limit set | 3/128 | SYR4 | 2012–2019 |
| Selenium | 3.1 µg/L 6.2% of the EPA limit 50 µg/L | 2/14 | SYR4 | 2012–2019 |
| Chromium | 5.4 µg/L 5.4% of the EPA limit 100 µg/L | 1/14 | SYR4 | 2012–2019 |
| Pentachlorophenol | 0.7200 µg/L 72% of the EPA limit 1 µg/L | 1/18 | SYR4 | 2012–2019 |
85 contaminants tested, none detected
Utility contact
Frequently asked questions about Jacksonville
Is Jacksonville tap water safe to drink?
EPA monitoring detected 24 contaminants in Jacksonville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Jacksonville's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Jacksonville serve?
Jacksonville reports serving 19,903 people in Illinois, per its EPA record.
Has Jacksonville had any water quality violations?
The EPA has 33 violations on file for Jacksonville, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.