← Illinois

Tap water quality report

Jacksonville

EPA monitoring tested this supplier for 109 contaminants and detected 24. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
24
detected
19,903
people served
4
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Morgan

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
33
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2011-05-01 → 2011-05-31
MCL Health-based Resolved 2011-05-01 → 2011-05-31
MCL Health-based Resolved 2011-05-01 → 2011-05-31
MCL Health-based Resolved 2011-05-01 → 2011-05-31
Other Monitoring Resolved 2011-07-16
Other Monitoring Resolved 2011-07-16
MR Monitoring Resolved 2011-06-01 → 2011-06-30
MR Monitoring Resolved 2011-06-01 → 2011-06-30
MR Monitoring Resolved 2011-06-01 → 2011-06-30
MR Monitoring Resolved 2011-06-01 → 2011-06-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0098 µg/L 4/4 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
24.5 µg/L
No EPA limit set
128/128 SYR4 2012–2019
Chloroform
66.1 µg/L
No EPA limit set
128/128 SYR4 2012–2019
Dibromochloromethane
15.9 µg/L
No EPA limit set
128/128 SYR4 2012–2019
TTHM
97.4 µg/L 122%
of the EPA limit, in the worst sample — 80 µg/L
128/128 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
28.6 µg/L 48%
of the EPA limit 60 µg/L
128/128 SYR4 2012–2019
Bromoform
4.4 µg/L
No EPA limit set
126/128 SYR4 2012–2019
Dibromoacetic Acid
5.9 µg/L
No EPA limit set
126/128 SYR4 2012–2019
Dichloroacetic Acid
17.5 µg/L
No EPA limit set
124/128 SYR4 2012–2019
Trichloroacetic Acid
8.9 µg/L
No EPA limit set
112/128 SYR4 2012–2019
Nitrate
1900 µg/L 19%
of the EPA limit 10000 µg/L
22/28 SYR4 2012–2019
Copper
19 µg/L 1.5%
of the EPA limit 1300 µg/L
21/60 SYR4 2014–2017
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
21/21 LCR 2025
Barium
140 µg/L 7%
of the EPA limit 2000 µg/L
14/14 SYR4 2012–2019
Monobromoacetic Acid
4.55 µg/L
No EPA limit set
14/128 SYR4 2012–2019
Fluoride
915 µg/L 23%
of the EPA limit 4000 µg/L
9/14 SYR4 2012–2019
Arsenic
9.4 µg/L 94%
of the EPA limit 10 µg/L
8/14 SYR4 2012–2019
Lead
2.3 µg/L 15%
of the EPA limit 15 µg/L
6/60 SYR4 2014–2017
Nitrate-Nitrite
1400 µg/L 14%
of the EPA limit 10000 µg/L
6/9 SYR4 2012–2019
Combined Radium (-226 And -228)
1.778 pCi/L 36%
of the EPA limit 5 pCi/L
3/3 SYR4 2014–2017
Monochloroacetic Acid
3.21 µg/L
No EPA limit set
3/128 SYR4 2012–2019
Selenium
3.1 µg/L 6.2%
of the EPA limit 50 µg/L
2/14 SYR4 2012–2019
Chromium
5.4 µg/L 5.4%
of the EPA limit 100 µg/L
1/14 SYR4 2012–2019
Pentachlorophenol
0.7200 µg/L 72%
of the EPA limit 1 µg/L
1/18 SYR4 2012–2019
85 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HEARIN, RICKY
Phone
217-479-4660
Email
rhearin@jacksonvilleil.gov

Frequently asked questions about Jacksonville

Is Jacksonville tap water safe to drink?

EPA monitoring detected 24 contaminants in Jacksonville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Jacksonville's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Jacksonville serve?

Jacksonville reports serving 19,903 people in Illinois, per its EPA record.

Has Jacksonville had any water quality violations?

The EPA has 33 violations on file for Jacksonville, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.