← Illinois

Tap water quality report

Glen Carbon

EPA monitoring tested this supplier for 44 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
17
detected
12,618
people served
0
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Madison

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
42
violations on file
1
still open
ViolationTypeStatusPeriod
Other Monitoring Unaddressed 2025-07-01
MR Monitoring Resolved 2024-07-01 → 2024-09-30
MR Monitoring Resolved 2024-07-01 → 2024-09-30
MR Monitoring Resolved 2024-07-01 → 2024-09-30
MR Monitoring Resolved 2024-07-01 → 2024-09-30
MR Monitoring Resolved 2019-01-01 → 2019-09-30
MR Monitoring Resolved 2019-01-01 → 2019-09-30
MR Monitoring Resolved 2019-01-01 → 2019-09-30
MR Monitoring Resolved 2019-01-01 → 2019-09-30
MR Monitoring Resolved 2019-01-01 → 2019-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0160 µg/L 4/4 2024
Pfhxa 0.0038 µg/L 1/4 2024
Pfpea 0.0036 µg/L 1/4 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
63000 µg/L 4846%
of the EPA limit, in the worst sample — 1300 µg/L
74/74 SYR4 2012–2019
Lead
240 µg/L 1600%
of the EPA limit, in the worst sample — 15 µg/L
34/74 SYR4 2012–2019
Bromodichloromethane
13 µg/L
No EPA limit set
31/31 SYR4 2013–2019
Chloroform
14 µg/L
No EPA limit set
31/31 SYR4 2013–2019
Dibromochloromethane
9.93 µg/L
No EPA limit set
31/31 SYR4 2013–2019
TTHM
37 µg/L 46%
of the EPA limit 80 µg/L
31/31 SYR4 2013–2019
Bromoform
2.45 µg/L
No EPA limit set
28/31 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
26/26 LCR 2025
Dibromoacetic Acid
4.88 µg/L
No EPA limit set
22/31 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
13.9 µg/L 23%
of the EPA limit 60 µg/L
22/31 SYR4 2013–2019
Trichloroacetic Acid
3.9 µg/L
No EPA limit set
14/31 SYR4 2013–2019
Dichloroacetic Acid
6.7 µg/L
No EPA limit set
8/31 SYR4 2013–2019
Monobromoacetic Acid
1.55 µg/L
No EPA limit set
1/31 SYR4 2013–2019
Lithium
9.42 µg/L
No EPA limit set
1/4 UCMR-5 2024
27 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaMonochloroacetic AcidNetfosaaNfdhaNmefosaaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfuna

Utility contact

Contact
SLEMER, SCOTT A.
Phone
618-288-2606
Email
SASLEMER@glencarbonil.gov

Frequently asked questions about Glen Carbon

Is Glen Carbon tap water safe to drink?

EPA monitoring detected 17 contaminants in Glen Carbon's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Glen Carbon's water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Glen Carbon serve?

Glen Carbon reports serving 12,618 people in Illinois, per its EPA record.

Has Glen Carbon had any water quality violations?

The EPA has 42 violations on file for Glen Carbon, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.