← Illinois

Tap water quality report

Willoway Terrace Mhp

EPA monitoring tested this supplier for 78 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

78
contaminants tested
17
detected
900
people served
4
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Cook

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
16
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 1992-11-01 → 1992-11-30
MCL Health-based Archived 1992-11-01 → 1992-11-30
MCL Health-based Archived 1992-11-01 → 1992-11-30
MCL Health-based Archived 1992-11-01 → 1992-11-30
MON Monitoring Resolved 2023-02-01 → 2023-02-28
MON Monitoring Resolved 2023-02-01 → 2023-02-28
MON Monitoring Resolved 2023-02-01 → 2023-02-28
MON Monitoring Resolved 2023-02-01 → 2023-02-28
MR Monitoring Resolved 2023-01-01 → 2023-03-31
MR Monitoring Resolved 2023-01-01 → 2023-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
103 µg/L 7.9%
of the EPA limit 1300 µg/L
worst single sample: 136 µg/L
21/40 SYR4 2012–2018
Lead
23.54 µg/L 157%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 42.5 µg/L
17/40 SYR4 2012–2018
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
15/15 LCR 2024
Barium
49.625 µg/L 2.5%
of the EPA limit 2000 µg/L
worst single sample: 58.5 µg/L
6/6 SYR4 2012–2018
Fluoride
429 µg/L 11%
of the EPA limit 4000 µg/L
worst single sample: 430 µg/L
6/6 SYR4 2012–2018
Dibromoacetic Acid
1.317 µg/L
No EPA limit set
worst single sample: 1.33 µg/L
3/7 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
9.653 µg/L 16%
of the EPA limit 60 µg/L
worst single sample: 10.2 µg/L
3/7 SYR4 2014–2019
Arsenic
1.78585 µg/L 18%
of the EPA limit 10 µg/L
worst single sample: 1.84 µg/L
2/6 SYR4 2012–2018
Combined Radium (-226 And -228)
1.37355 pCi/L 27%
of the EPA limit 5 pCi/L
worst single sample: 1.4 pCi/L
2/2 SYR4 2014
Dichloroacetic Acid
1.068 µg/L
No EPA limit set
worst single sample: 1.07 µg/L
2/7 SYR4 2014–2019
Monochloroacetic Acid
7.5265 µg/L
No EPA limit set
worst single sample: 7.76 µg/L
2/7 SYR4 2014–2019
Nitrate
50 µg/L 0.5%
of the EPA limit 10000 µg/L
2/36 SYR4 2012–2019
Bromodichloromethane
1.61 µg/L
No EPA limit set
1/7 SYR4 2014–2019
Chloroform
1.99 µg/L
No EPA limit set
1/7 SYR4 2014–2019
Dibromochloromethane
1.5 µg/L
No EPA limit set
1/7 SYR4 2014–2019
Nitrate-Nitrite
50 µg/L 0.5%
of the EPA limit 10000 µg/L
1/6 SYR4 2012–2019
TTHM
5.1 µg/L 6.4%
of the EPA limit 80 µg/L
1/7 SYR4 2014–2019
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SMITH, JENNIFER
Phone
773-499-7255
Email
licenses@zemanhomes.com

Frequently asked questions about Willoway Terrace Mhp

Is Willoway Terrace Mhp tap water safe to drink?

EPA monitoring detected 17 contaminants in Willoway Terrace Mhp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Willoway Terrace Mhp's water?

EPA monitoring detected Copper, Lead, Lead, Barium, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Willoway Terrace Mhp serve?

Willoway Terrace Mhp reports serving 900 people in Illinois, per its EPA record.

Has Willoway Terrace Mhp had any water quality violations?

The EPA has 16 violations on file for Willoway Terrace Mhp, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.