Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-07-01 → 2019-09-30 |
| MCL | Health-based | Resolved | 2019-04-01 → 2019-06-30 |
| MCL | Health-based | Resolved | 2019-04-01 → 2019-06-30 |
| MCL | Health-based | Resolved | 2019-04-01 → 2019-06-30 |
| MCL | Health-based | Resolved | 2019-04-01 → 2019-06-30 |
| MCL | Health-based | Archived | 2013-10-01 → 2022-09-30 |
| MCL | Health-based | Archived | 2013-10-01 → 2022-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 14 µg/L No EPA limit set | 47/47 | SYR4 | 2012–2019 |
| Chloroform | 100 µg/L No EPA limit set | 47/47 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 25 µg/L No EPA limit set | 47/47 | SYR4 | 2012–2019 |
| TTHM | 110 µg/L 138% of the EPA limit, in the worst sample — 80 µg/L | 47/47 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 59 µg/L 98% of the EPA limit 60 µg/L | 47/47 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 36 µg/L No EPA limit set | 47/47 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.1 µg/L No EPA limit set | 33/47 | SYR4 | 2012–2019 |
| Copper | 1350 µg/L 104% of the EPA limit, in the worst sample — 1300 µg/L | 29/30 | SYR4 | 2014–2018 |
| Nitrate | 3469 µg/L 35% of the EPA limit 10000 µg/L | 18/18 | SYR4 | 2012–2019 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2024 |
| Arsenic | 8 µg/L 80% of the EPA limit 10 µg/L | 4/4 | SYR4 | 2013–2019 |
| Lead | 1 µg/L 6.7% of the EPA limit 15 µg/L | 3/30 | SYR4 | 2014–2018 |
| Nitrite | 100 µg/L 10% of the EPA limit 1000 µg/L | 2/25 | SYR4 | 2012–2019 |
| Barium | 900 µg/L 45% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2013 |
| Fluoride | 360 µg/L 9% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2013 |
| Monochloroacetic Acid | 4 µg/L No EPA limit set | 1/47 | SYR4 | 2012–2019 |
44 contaminants tested, none detected
Utility contact
Frequently asked questions about Woodward Water Supply
Is Woodward Water Supply tap water safe to drink?
EPA monitoring detected 16 contaminants in Woodward Water Supply's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Woodward Water Supply's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Woodward Water Supply serve?
Woodward Water Supply reports serving 1,346 people in Iowa, per its EPA record.
Has Woodward Water Supply had any water quality violations?
The EPA has 48 violations on file for Woodward Water Supply, of which 23 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.