← Florida

Tap water quality report

Lake Alfred, City of

EPA monitoring tested this supplier for 100 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

100
contaminants tested
18
detected
5,584
people served
1
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Polk

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1
health-based violations
41
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 1999-10-01 → 1999-12-31
MON Monitoring Archived 2024-08-01 → 2024-08-31
MON Monitoring Resolved 2024-07-01 → 2024-07-31
MON Monitoring Resolved 2024-06-01 → 2024-06-30
MON Monitoring Resolved 2024-04-01 → 2024-04-30
MON Monitoring Resolved 2024-03-01 → 2024-03-31
MON Monitoring Resolved 2023-10-01 → 2023-10-31
MON Monitoring Resolved 2023-09-01 → 2023-09-30
MON Monitoring Resolved 2023-09-01 → 2023-09-30
MON Monitoring Resolved 2023-08-01 → 2023-08-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFHXS 0.0047 µg/L 2/2 2024
PFOS 0.0067 µg/L 2/2 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
976 µg/L 24%
of the EPA limit 4000 µg/L
117/126 SYR4 2012–2019
Nitrate
2080 µg/L 21%
of the EPA limit 10000 µg/L
40/40 SYR4 2012–2019
TTHM
108.7 µg/L 136%
of the EPA limit, in the worst sample — 80 µg/L
20/20 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
48.3 µg/L 81%
of the EPA limit 60 µg/L
20/20 SYR4 2012–2019
Lead
0.0018 mg/L 12%
of the EPA limit 0.0150 mg/L
13/13 LCR 2023
Barium
21 µg/L 1.1%
of the EPA limit 2000 µg/L
4/4 SYR4 2014–2017
Copper
2.5 µg/L 0.2%
of the EPA limit 1300 µg/L
4/4 SYR4 2014–2017
Chromium
2.3 µg/L 2.3%
of the EPA limit 100 µg/L
4/4 SYR4 2014–2017
Cyanide
7.4 µg/L 3.7%
of the EPA limit 200 µg/L
3/4 SYR4 2014–2017
Arsenic
2.2 µg/L 22%
of the EPA limit 10 µg/L
2/4 SYR4 2014–2017
Dalapon
0.8400 µg/L 0.4%
of the EPA limit 200 µg/L
2/6 SYR4 2014–2017
Selenium
3.3 µg/L 6.6%
of the EPA limit 50 µg/L
2/4 SYR4 2014–2017
Combined Uranium
0.6705 µg/L 2.2%
of the EPA limit 30 µg/L
1/1 SYR4 2012
Nitrite
165 µg/L 17%
of the EPA limit 1000 µg/L
1/19 SYR4 2012–2019
Thallium, Total
0.4000 µg/L 20%
of the EPA limit 2 µg/L
1/4 SYR4 2014–2017
Toxaphene
0.5100 µg/L 17%
of the EPA limit 3 µg/L
1/6 SYR4 2014–2017
82 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPfmbaPfmpaPFNAPFOAPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)TrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CITY OF LAKE ALFRED
Phone
863-291-5274

Frequently asked questions about Lake Alfred, City of

Is Lake Alfred, City of tap water safe to drink?

EPA monitoring detected 18 contaminants in Lake Alfred, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Lake Alfred, City of's water?

EPA monitoring detected Fluoride, Nitrate, TTHM, Total Haloacetic Acids (HAA5), Lead, and others. The full list with the level and data source for each is above.

How many people does Lake Alfred, City of serve?

Lake Alfred, City of reports serving 5,584 people in Florida, per its EPA record.

Has Lake Alfred, City of had any water quality violations?

The EPA has 41 violations on file for Lake Alfred, City of, of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.