Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2006-11-26 → 2006-12-31 |
| MCL | Health-based | Archived | 1995-05-01 → 1995-05-31 |
| MCL | Health-based | Archived | 1995-05-01 → 1995-05-31 |
| MCL | Health-based | Archived | 1995-05-01 → 1995-05-31 |
| MR | Monitoring | Archived | 2026-03-01 → 2026-03-31 |
| MON | Monitoring | Archived | 2026-03-01 → 2026-03-31 |
| MR | Monitoring | Archived | 2026-02-01 → 2026-02-28 |
| MON | Monitoring | Archived | 2026-02-01 → 2026-02-28 |
| MON | Monitoring | Archived | 2026-01-01 → 2026-01-31 |
| MR | Monitoring | Archived | 2026-01-01 → 2026-01-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 9070 µg/L 91% of the EPA limit 10000 µg/L | 140/144 | SYR4 | 2012–2019 |
| TTHM | 27.5 µg/L 34% of the EPA limit 80 µg/L | 17/17 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 19.4 µg/L 32% of the EPA limit 60 µg/L | 15/15 | SYR4 | 2012–2019 |
| Fluoride | 200 µg/L 5% of the EPA limit 4000 µg/L | 14/14 | SYR4 | 2012–2018 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2024 |
| Nitrite | 220 µg/L 22% of the EPA limit 1000 µg/L | 8/20 | SYR4 | 2012–2019 |
| Barium | 18 µg/L 0.9% of the EPA limit 2000 µg/L | 7/7 | SYR4 | 2012–2018 |
| Copper | 8.9 µg/L 0.7% of the EPA limit 1300 µg/L | 7/7 | SYR4 | 2012–2018 |
| Selenium | 8.4 µg/L 17% of the EPA limit 50 µg/L | 7/7 | SYR4 | 2012–2018 |
| Arsenic | 3.9 µg/L 39% of the EPA limit 10 µg/L | 6/7 | SYR4 | 2012–2018 |
| Chromium | 7.5 µg/L 7.5% of the EPA limit 100 µg/L | 5/7 | SYR4 | 2012–2018 |
| Combined Uranium | 2.9949 µg/L 10% of the EPA limit 30 µg/L | 3/3 | SYR4 | 2012–2015 |
| Di(2-ethylhexyl) Phthalate | 7.5 µg/L 125% of the EPA limit, in the worst sample — 6 µg/L | 2/10 | SYR4 | 2012–2019 |
| Heptachlor Epoxide | 0.0210 µg/L 11% of the EPA limit 0.2000 µg/L | 2/6 | SYR4 | 2012–2018 |
| Toluene | 5.1 µg/L 0.5% of the EPA limit 1000 µg/L | 2/14 | SYR4 | 2012–2019 |
| Antimony, Total | 0.1000 µg/L 1.7% of the EPA limit 6 µg/L | 1/7 | SYR4 | 2012–2018 |
| Beryllium, Total | 0.2000 µg/L 5% of the EPA limit 4 µg/L | 1/7 | SYR4 | 2012–2018 |
| Glyphosate | 4.2 µg/L 0.6% of the EPA limit 700 µg/L | 1/6 | SYR4 | 2012–2018 |
| Lead | 0.3000 µg/L 2% of the EPA limit 15 µg/L | 1/7 | SYR4 | 2012–2018 |
| Thallium, Total | 0.2000 µg/L 10% of the EPA limit 2 µg/L | 1/7 | SYR4 | 2012–2018 |
50 contaminants tested, none detected
Utility contact
Frequently asked questions about Crestridge Utilities
Is Crestridge Utilities tap water safe to drink?
EPA monitoring detected 20 contaminants in Crestridge Utilities's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Crestridge Utilities's water?
EPA monitoring detected Nitrate, TTHM, Total Haloacetic Acids (HAA5), Fluoride, Lead, and others. The full list with the level and data source for each is above.
How many people does Crestridge Utilities serve?
Crestridge Utilities reports serving 1,209 people in Florida, per its EPA record.
Has Crestridge Utilities had any water quality violations?
The EPA has 52 violations on file for Crestridge Utilities, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.