← Florida

Tap water quality report

Sunset Acres

EPA monitoring tested this supplier for 69 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

69
contaminants tested
11
detected
69
people served
1
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Lee

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

1
health-based violations
33
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 1997-06-01 → 1997-06-30
MON Monitoring Resolved 2026-02-01 → 2026-02-28
MON Monitoring Resolved 2026-02-01 → 2026-02-28
MON Monitoring Resolved 2026-02-01 → 2026-02-28
MR Monitoring Resolved 2026-02-01 → 2026-02-28
MR Monitoring Resolved 2026-02-01 → 2026-02-28
MR Monitoring Resolved 2026-02-01 → 2026-02-28
MR Monitoring Resolved 2026-01-01 → 2026-01-31
MR Monitoring Resolved 2026-01-01 → 2026-01-31
MR Monitoring Resolved 2026-01-01 → 2026-01-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.00050 mg/L 3.3%
of the EPA limit 0.0150 mg/L
16/16 LCR 2024
TTHM
59.4 µg/L 74%
of the EPA limit 80 µg/L
14/14 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
4.9 µg/L 8.2%
of the EPA limit 60 µg/L
14/14 SYR4 2012–2019
Nitrate
247 µg/L 2.5%
of the EPA limit 10000 µg/L
10/20 SYR4 2012–2019
Fluoride
1300 µg/L 33%
of the EPA limit 4000 µg/L
6/6 SYR4 2012–2018
Barium
7.6 µg/L 0.4%
of the EPA limit 2000 µg/L
3/3 SYR4 2012–2018
Copper
4 µg/L 0.3%
of the EPA limit 1300 µg/L
3/3 SYR4 2012–2018
Nitrite
20 µg/L 2%
of the EPA limit 1000 µg/L
2/10 SYR4 2012–2019
Cadmium
1 µg/L 20%
of the EPA limit 5 µg/L
1/3 SYR4 2012–2018
Chromium
2 µg/L 2%
of the EPA limit 100 µg/L
1/3 SYR4 2012–2018
Lead
0.5000 µg/L 3.3%
of the EPA limit 15 µg/L
1/3 SYR4 2012–2018
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DANNY KANE
Phone
561-492-7382

Frequently asked questions about Sunset Acres

Is Sunset Acres tap water safe to drink?

EPA monitoring detected 11 contaminants in Sunset Acres's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Sunset Acres's water?

EPA monitoring detected Lead, TTHM, Total Haloacetic Acids (HAA5), Nitrate, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Sunset Acres serve?

Sunset Acres reports serving 69 people in Florida, per its EPA record.

Has Sunset Acres had any water quality violations?

The EPA has 33 violations on file for Sunset Acres, of which 1 is health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.