Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2025-02-01 |
| MCL | Health-based | Resolved | 2015-11-01 → 2015-11-30 |
| MCL | Health-based | Resolved | 2015-11-01 → 2015-11-30 |
| MCL | Health-based | Resolved | 2015-11-01 → 2015-11-30 |
| MCL | Health-based | Archived | 2006-04-01 → 2006-06-30 |
| MCL | Health-based | Archived | 2006-04-01 → 2006-06-30 |
| MCL | Health-based | Archived | 2002-06-01 → 2002-06-30 |
| MCL | Health-based | Archived | 2002-06-01 → 2002-06-30 |
| RPT | Monitoring | Unaddressed | 2025-02-01 |
| MON | Monitoring | Resolved | 2024-09-01 → 2024-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Lead | 0.0031 mg/L 21% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Nitrate | 894 µg/L 8.9% of the EPA limit 10000 µg/L | 12/16 | SYR4 | 2012–2019 |
| TTHM | 39.905 µg/L 50% of the EPA limit 80 µg/L
worst single sample: 47.5 µg/L | 8/8 | SYR4 | 2014–2019 |
| Dalapon | 2.42 µg/L 1.2% of the EPA limit 200 µg/L
worst single sample: 2.5 µg/L | 5/9 | SYR4 | 2012–2017 |
| Total Haloacetic Acids (HAA5) | 20.98 µg/L 35% of the EPA limit 60 µg/L
worst single sample: 24 µg/L | 5/8 | SYR4 | 2014–2019 |
| Fluoride | 220 µg/L 5.5% of the EPA limit 4000 µg/L | 4/4 | SYR4 | 2014–2017 |
| Nitrite | 360.15 µg/L 36% of the EPA limit 1000 µg/L
worst single sample: 369 µg/L | 4/8 | SYR4 | 2012–2019 |
| Barium | 23.89 µg/L 1.2% of the EPA limit 2000 µg/L
worst single sample: 24.2 µg/L | 2/2 | SYR4 | 2014–2017 |
| Dichloromethane | 5.33 µg/L 107% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 5.6 µg/L | 2/9 | SYR4 | 2014–2018 |
| Copper | 34 µg/L 2.6% of the EPA limit 1300 µg/L | 1/2 | SYR4 | 2014–2017 |
| Cyanide | 6.1 µg/L 3.1% of the EPA limit 200 µg/L | 1/2 | SYR4 | 2014–2017 |
| Chromium | 1 µg/L 1% of the EPA limit 100 µg/L | 1/2 | SYR4 | 2014–2017 |
| Lead | 14 µg/L 93% of the EPA limit 15 µg/L | 1/2 | SYR4 | 2014–2017 |
| Selenium | 2.6 µg/L 5.2% of the EPA limit 50 µg/L | 1/2 | SYR4 | 2014–2017 |
| Lithium | 9.48 µg/L No EPA limit set | 1/2 | UCMR-5 | 2025 |
83 contaminants tested, none detected
Utility contact
Frequently asked questions about Moore Haven Wtp
Is Moore Haven Wtp tap water safe to drink?
EPA monitoring detected 15 contaminants in Moore Haven Wtp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Moore Haven Wtp's water?
EPA monitoring detected Lead, Nitrate, TTHM, Dalapon, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Moore Haven Wtp serve?
Moore Haven Wtp reports serving 3,735 people in Florida, per its EPA record.
Has Moore Haven Wtp had any water quality violations?
The EPA has 14 violations on file for Moore Haven Wtp, of which 8 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.