← Florida

Tap water quality report

Hammock Pointe Utility Association Inc

EPA monitoring tested this supplier for 68 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

68
contaminants tested
10
detected
515
people served
56
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Osceola

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

56
health-based violations
106
violations on file
3
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2025-02-01
MCL Health-based Resolved 2020-01-01 → 2020-03-31
MCL Health-based Resolved 2020-01-01 → 2020-03-31
MCL Health-based Resolved 2020-01-01 → 2020-03-31
MCL Health-based Resolved 2019-10-01 → 2019-12-31
MCL Health-based Resolved 2019-10-01 → 2019-12-31
MCL Health-based Resolved 2019-10-01 → 2019-12-31
MCL Health-based Resolved 2019-10-01 → 2019-12-31
MCL Health-based Resolved 2019-10-01 → 2019-12-31
MCL Health-based Resolved 2019-07-01 → 2019-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
165.253 µg/L 207%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 178.62 µg/L
27/27 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
82.59 µg/L 138%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 90.14 µg/L
27/27 SYR4 2012–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
21/21 LCR 2024
Nitrate
260 µg/L 2.6%
of the EPA limit 10000 µg/L
10/18 SYR4 2012–2019
Fluoride
260 µg/L 6.5%
of the EPA limit 4000 µg/L
6/6 SYR4 2012–2018
Barium
7.68 µg/L 0.4%
of the EPA limit 2000 µg/L
worst single sample: 7.7 µg/L
3/3 SYR4 2012–2018
Arsenic
0.2000 µg/L 2%
of the EPA limit 10 µg/L
1/3 SYR4 2012–2018
Copper
5.6 µg/L 0.4%
of the EPA limit 1300 µg/L
1/3 SYR4 2012–2018
Lead
0.1000 µg/L 0.7%
of the EPA limit 15 µg/L
1/3 SYR4 2012–2018
Selenium
0.9000 µg/L 1.8%
of the EPA limit 50 µg/L
1/3 SYR4 2012–2018
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
AIDA GONZALEZ
Phone
407-770-1748

Frequently asked questions about Hammock Pointe Utility Association Inc

Is Hammock Pointe Utility Association Inc tap water safe to drink?

EPA monitoring detected 10 contaminants in Hammock Pointe Utility Association Inc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Hammock Pointe Utility Association Inc's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Nitrate, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Hammock Pointe Utility Association Inc serve?

Hammock Pointe Utility Association Inc reports serving 515 people in Florida, per its EPA record.

Has Hammock Pointe Utility Association Inc had any water quality violations?

The EPA has 106 violations on file for Hammock Pointe Utility Association Inc, of which 56 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.