← Florida

Tap water quality report

Villages of Ocala

EPA monitoring tested this supplier for 39 contaminants and detected 10. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

39
contaminants tested
10
detected
132
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Marion

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
62
violations on file
0
still open
ViolationTypeStatusPeriod
MR Monitoring Resolved 2019-01-01
MR Monitoring Resolved 2016-04-01 → 2016-04-30
MR Monitoring Resolved 2015-10-01 → 2015-10-31
MR Monitoring Resolved 2015-10-01 → 2015-10-31
MR Monitoring Resolved 2015-10-01 → 2015-10-31
MR Monitoring Resolved 2014-03-01 → 2014-03-31
Other Monitoring Resolved 2012-08-01
MR Monitoring Resolved 2012-01-01 → 2012-12-31
MR Monitoring Resolved 2012-01-01 → 2012-12-31
Other Monitoring Resolved 2011-08-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
15/15 LCR 2025
Nitrate
3800 µg/L 38%
of the EPA limit 10000 µg/L
14/14 SYR4 2013–2019
Fluoride
130 µg/L 3.3%
of the EPA limit 4000 µg/L
4/4 SYR4 2015–2018
TTHM
31.336 µg/L 39%
of the EPA limit 80 µg/L
worst single sample: 34.43 µg/L
3/4 SYR4 2012–2018
Arsenic
1.79 µg/L 18%
of the EPA limit 10 µg/L
worst single sample: 1.8 µg/L
2/2 SYR4 2015–2018
Barium
3.185 µg/L 0.2%
of the EPA limit 2000 µg/L
worst single sample: 3.2 µg/L
2/2 SYR4 2015–2018
Total Haloacetic Acids (HAA5)
14.289 µg/L 24%
of the EPA limit 60 µg/L
worst single sample: 15 µg/L
2/4 SYR4 2012–2018
Antimony, Total
0.4000 µg/L 6.7%
of the EPA limit 6 µg/L
1/2 SYR4 2015–2018
Copper
0.7000 µg/L 0.1%
of the EPA limit 1300 µg/L
1/2 SYR4 2015–2018
Chromium
1.1 µg/L 1.1%
of the EPA limit 100 µg/L
1/2 SYR4 2015–2018
29 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-DichloropropaneBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbon TetrachlorideDichloromethaneEthylbenzeneLeadMercuryNitriteSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
JAMES C. GOSS
Phone
813-285-4083

Frequently asked questions about Villages of Ocala

Is Villages of Ocala tap water safe to drink?

EPA monitoring detected 10 contaminants in Villages of Ocala's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Villages of Ocala's water?

EPA monitoring detected Lead, Nitrate, Fluoride, TTHM, Arsenic, and others. The full list with the level and data source for each is above.

How many people does Villages of Ocala serve?

Villages of Ocala reports serving 132 people in Florida, per its EPA record.