Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2017-01-01 → 2017-12-31 |
| MR | Monitoring | Resolved | 2016-01-01 |
| MR | Monitoring | Resolved | 2015-01-01 → 2015-12-31 |
| MR | Monitoring | Resolved | 2015-01-01 → 2015-12-31 |
| MR | Monitoring | Resolved | 2015-01-01 → 2015-12-31 |
| MR | Monitoring | Resolved | 2015-01-01 → 2015-12-31 |
| MR | Monitoring | Resolved | 2015-01-01 → 2015-12-31 |
| MR | Monitoring | Resolved | 2015-01-01 → 2015-12-31 |
| MR | Monitoring | Resolved | 2015-01-01 → 2015-12-31 |
| MR | Monitoring | Resolved | 2015-01-01 → 2015-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1680 µg/L 17% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0018 mg/L 12% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2024 |
| Fluoride | 180 µg/L 4.5% of the EPA limit 4000 µg/L | 6/6 | SYR4 | 2012–2018 |
| TTHM | 3.112 µg/L 3.9% of the EPA limit 80 µg/L
worst single sample: 3.44 µg/L | 5/9 | SYR4 | 2012–2019 |
| Arsenic | 2.39 µg/L 24% of the EPA limit 10 µg/L
worst single sample: 2.5 µg/L | 3/3 | SYR4 | 2012–2018 |
| Barium | 6.19 µg/L 0.3% of the EPA limit 2000 µg/L
worst single sample: 6.2 µg/L | 3/3 | SYR4 | 2012–2018 |
| Copper | 3.61 µg/L 0.3% of the EPA limit 1300 µg/L
worst single sample: 3.7 µg/L | 3/3 | SYR4 | 2012–2018 |
| Selenium | 2.8 µg/L 5.6% of the EPA limit 50 µg/L
worst single sample: 2.9 µg/L | 3/3 | SYR4 | 2012–2018 |
| Total Haloacetic Acids (HAA5) | 5.39 µg/L 9% of the EPA limit 60 µg/L
worst single sample: 5.53 µg/L | 3/9 | SYR4 | 2012–2019 |
| Chromium | 9.565 µg/L 9.6% of the EPA limit 100 µg/L
worst single sample: 10 µg/L | 2/3 | SYR4 | 2012–2018 |
| Lead | 0.2900 µg/L 1.9% of the EPA limit 15 µg/L
worst single sample: 0.3000 µg/L | 2/3 | SYR4 | 2012–2018 |
| Antimony, Total | 0.1000 µg/L 1.7% of the EPA limit 6 µg/L | 1/3 | SYR4 | 2012–2018 |
| Cyanide | 6.3 µg/L 3.2% of the EPA limit 200 µg/L | 1/3 | SYR4 | 2012–2018 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Pine Ridge Estates
Is Pine Ridge Estates tap water safe to drink?
EPA monitoring detected 13 contaminants in Pine Ridge Estates's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pine Ridge Estates's water?
EPA monitoring detected Nitrate, Lead, Fluoride, TTHM, Arsenic, and others. The full list with the level and data source for each is above.
How many people does Pine Ridge Estates serve?
Pine Ridge Estates reports serving 531 people in Florida, per its EPA record.
Has Pine Ridge Estates had any water quality violations?
The EPA has 17 violations on file for Pine Ridge Estates, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.