← Florida

Tap water quality report

Ocala East Villas

EPA monitoring tested this supplier for 68 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

68
contaminants tested
11
detected
608
people served
6
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Marion

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

6
health-based violations
18
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2009-09-01 → 2009-09-30
MCL Health-based Resolved 2009-09-01 → 2009-09-30
MCL Health-based Resolved 2009-09-01 → 2009-09-30
MCL Health-based Archived 2003-02-01 → 2003-02-28
MCL Health-based Resolved 1993-07-01 → 1993-07-31
MCL Health-based Resolved 1993-07-01 → 1993-07-31
MR Monitoring Archived 2000-07-01 → 2000-07-31
MR Monitoring Archived 1995-06-01 → 1995-06-30
MR Monitoring Archived 1993-08-01 → 1993-08-31
MR Monitoring Archived 1991-05-01 → 1991-05-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
2400 µg/L 24%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
13/13 LCR 2024
Fluoride
140 µg/L 3.5%
of the EPA limit 4000 µg/L
6/6 SYR4 2012–2018
Total Haloacetic Acids (HAA5)
4.971 µg/L 8.3%
of the EPA limit 60 µg/L
worst single sample: 5.01 µg/L
4/9 SYR4 2012–2019
Arsenic
0.5800 µg/L 5.8%
of the EPA limit 10 µg/L
worst single sample: 0.6000 µg/L
3/3 SYR4 2012–2018
Barium
4.64 µg/L 0.2%
of the EPA limit 2000 µg/L
worst single sample: 4.7 µg/L
3/3 SYR4 2012–2018
TTHM
4.481 µg/L 5.6%
of the EPA limit 80 µg/L
worst single sample: 4.62 µg/L
3/9 SYR4 2012–2019
Copper
0.9000 µg/L 0.1%
of the EPA limit 1300 µg/L
1/3 SYR4 2012–2018
Cyanide
9.6 µg/L 4.8%
of the EPA limit 200 µg/L
1/3 SYR4 2012–2018
Chromium
1.2 µg/L 1.2%
of the EPA limit 100 µg/L
1/3 SYR4 2012–2018
Selenium
0.7000 µg/L 1.4%
of the EPA limit 50 µg/L
1/3 SYR4 2012–2018
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
OCALA EAST VILLAS INC
Phone
352-236-4759

Frequently asked questions about Ocala East Villas

Is Ocala East Villas tap water safe to drink?

EPA monitoring detected 11 contaminants in Ocala East Villas's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Ocala East Villas's water?

EPA monitoring detected Nitrate, Lead, Fluoride, Total Haloacetic Acids (HAA5), Arsenic, and others. The full list with the level and data source for each is above.

How many people does Ocala East Villas serve?

Ocala East Villas reports serving 608 people in Florida, per its EPA record.

Has Ocala East Villas had any water quality violations?

The EPA has 18 violations on file for Ocala East Villas, of which 6 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.