← Florida

Tap water quality report

Hermits Cove Water

EPA monitoring tested this supplier for 69 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

69
contaminants tested
11
detected
558
people served
17
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Putnam

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

17
health-based violations
37
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2015-09-01 → 2015-09-30
MCL Health-based Resolved 2007-04-01 → 2007-04-30
MCL Health-based Archived 2005-01-01 → 2005-03-31
MCL Health-based Archived 1989-02-01 → 1993-01-31
MCL Health-based Archived 1989-02-01 → 1993-01-31
MCL Health-based Archived 1989-02-01 → 1993-01-31
MCL Health-based Archived 1989-02-01 → 1993-01-31
MCL Health-based Archived 1989-02-01 → 1993-01-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
104.009 µg/L 130%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 163.4 µg/L
19/21 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
25.709 µg/L 43%
of the EPA limit 60 µg/L
worst single sample: 26.78 µg/L
19/21 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
13/13 LCR 2024
Nitrate
88 µg/L 0.9%
of the EPA limit 10000 µg/L
6/18 SYR4 2012–2019
Fluoride
240 µg/L 6%
of the EPA limit 4000 µg/L
4/6 SYR4 2012–2018
Barium
14.9 µg/L 0.7%
of the EPA limit 2000 µg/L
worst single sample: 15 µg/L
3/3 SYR4 2012–2018
Copper
2.67 µg/L 0.2%
of the EPA limit 1300 µg/L
worst single sample: 2.7 µg/L
3/3 SYR4 2012–2018
Arsenic
0.6000 µg/L 6%
of the EPA limit 10 µg/L
1/3 SYR4 2012–2018
Cyanide
200 µg/L 100%
of the EPA limit 200 µg/L
1/3 SYR4 2012–2018
Cadmium
0.2000 µg/L 4%
of the EPA limit 5 µg/L
1/3 SYR4 2012–2018
Selenium
2.8 µg/L 5.6%
of the EPA limit 50 µg/L
1/3 SYR4 2012–2018
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SAM CAIN, P.E.
Phone
407-629-6900

Frequently asked questions about Hermits Cove Water

Is Hermits Cove Water tap water safe to drink?

EPA monitoring detected 11 contaminants in Hermits Cove Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Hermits Cove Water's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Nitrate, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Hermits Cove Water serve?

Hermits Cove Water reports serving 558 people in Florida, per its EPA record.

Has Hermits Cove Water had any water quality violations?

The EPA has 37 violations on file for Hermits Cove Water, of which 17 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.