Tap water quality report

Wild Quail Pump District

EPA monitoring tested this supplier for 76 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

76
contaminants tested
20
detected
1,017
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Kent

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
1
violations on file
0
still open
ViolationTypeStatusPeriod
Other Monitoring Resolved 2002-07-01 → 2002-07-25

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the single worst sample on record — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
140 µg/L 11%
of the EPA limit 1300 µg/L
33/33 SYR4 2013–2019
Dibromochloromethane
4.93 µg/L
No EPA limit set
25/41 SYR4 2012–2019
Dichloroacetic Acid
18.222 µg/L
No EPA limit set
25/25 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
46.764 µg/L 78%
of the EPA limit 60 µg/L
25/25 SYR4 2013–2019
Bromodichloromethane
11.8 µg/L
No EPA limit set
24/41 SYR4 2012–2019
Chloroform
79.95 µg/L
No EPA limit set
24/41 SYR4 2012–2019
Trichloroacetic Acid
30.984 µg/L
No EPA limit set
24/25 SYR4 2013–2019
TTHM
90.85 µg/L 114%
of the EPA limit, in the worst sample — 80 µg/L
22/22 SYR4 2013–2019
Nitrate
5600 µg/L 56%
of the EPA limit 10000 µg/L
16/32 SYR4 2012–2019
Lead
0.00048 mg/L 3.2%
of the EPA limit 0.0150 mg/L
14/14 LCR 2024
Dalapon
2.2 µg/L 1.1%
of the EPA limit 200 µg/L
12/19 SYR4 2012–2019
Lead
7.9 µg/L 53%
of the EPA limit 15 µg/L
9/37 SYR4 2012–2019
Bromoform
1.78 µg/L
No EPA limit set
8/41 SYR4 2012–2019
Fluoride
758.1 µg/L 19%
of the EPA limit 4000 µg/L
8/16 SYR4 2012–2019
Nitrate-Nitrite
5600 µg/L 56%
of the EPA limit 10000 µg/L
8/16 SYR4 2012–2019
Monochloroacetic Acid
1.686 µg/L
No EPA limit set
6/25 SYR4 2013–2019
Chromium
4.1 µg/L 4.1%
of the EPA limit 100 µg/L
4/4 SYR4 2012–2015
Dibromoacetic Acid
1.77 µg/L
No EPA limit set
3/25 SYR4 2013–2019
Arsenic
2.4 µg/L 24%
of the EPA limit 10 µg/L
2/4 SYR4 2012–2015
Barium
143.1 µg/L 7.2%
of the EPA limit 2000 µg/L
2/4 SYR4 2012–2015
56 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined Radium (-226 And -228)DichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Frequently asked questions about Wild Quail Pump District

Is Wild Quail Pump District tap water safe to drink?

EPA monitoring detected 20 contaminants in Wild Quail Pump District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Wild Quail Pump District's water?

EPA monitoring detected Copper, Dibromochloromethane, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Wild Quail Pump District serve?

Wild Quail Pump District reports serving 1,017 people, per its EPA record.

Has Wild Quail Pump District had any water quality violations?

The EPA has 1 violation on file for Wild Quail Pump District, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.