Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2008-07-01 → 2008-07-31 |
| MCL | Health-based | Resolved | 2008-07-01 → 2008-07-31 |
| MCL | Health-based | Resolved | 2008-07-01 → 2008-07-31 |
| MCL | Health-based | Resolved | 2008-07-01 → 2008-07-31 |
| MCL | Health-based | Resolved | 2007-08-01 → 2007-08-31 |
| MCL | Health-based | Resolved | 2007-08-01 → 2007-08-31 |
| MCL | Health-based | Resolved | 2007-08-01 → 2007-08-31 |
| MCL | Health-based | Resolved | 2007-08-01 → 2007-08-31 |
| MCL | Health-based | Resolved | 2000-06-01 → 2000-06-30 |
| MCL | Health-based | Resolved | 2000-06-01 → 2000-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 640 µg/L 49% of the EPA limit 1300 µg/L | 60/60 | SYR4 | 2013–2019 |
| TTHM | 66.5 µg/L 83% of the EPA limit 80 µg/L | 57/57 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 44.7 µg/L 75% of the EPA limit 60 µg/L | 56/57 | SYR4 | 2012–2019 |
| Nitrate | 4930 µg/L 49% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2025 |
| Nitrate-Nitrite | 4930 µg/L 49% of the EPA limit 10000 µg/L | 8/8 | SYR4 | 2012–2019 |
| Lead | 16 µg/L 107% of the EPA limit, in the worst sample — 15 µg/L | 7/60 | SYR4 | 2013–2019 |
| Barium | 340 µg/L 17% of the EPA limit 2000 µg/L | 3/3 | SYR4 | 2012–2018 |
| Chloroform | 7.7 µg/L No EPA limit set | 2/8 | SYR4 | 2012–2019 |
| Bromodichloromethane | 4.3 µg/L No EPA limit set | 1/8 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.9 µg/L No EPA limit set | 1/8 | SYR4 | 2012–2019 |
93 contaminants tested, none detected
Utility contact
Frequently asked questions about Portland Water Department
Is Portland Water Department tap water safe to drink?
EPA monitoring detected 13 contaminants in Portland Water Department's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Portland Water Department's water?
EPA monitoring detected Copper, TTHM, Total Haloacetic Acids (HAA5), Nitrate, Lead, and others. The full list with the level and data source for each is above.
How many people does Portland Water Department serve?
Portland Water Department reports serving 5,010 people in Connecticut, per its EPA record.
Has Portland Water Department had any water quality violations?
The EPA has 47 violations on file for Portland Water Department, of which 24 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.