Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1996-07-01 → 1996-07-31 |
| MCL | Health-based | Resolved | 1996-07-01 → 1996-07-31 |
| MCL | Health-based | Resolved | 1996-07-01 → 1996-07-31 |
| MCL | Health-based | Resolved | 1996-07-01 → 1996-07-31 |
| MR | Monitoring | Resolved | 2022-01-01 |
| MR | Monitoring | Resolved | 2022-01-01 |
| MR | Monitoring | Resolved | 2022-01-01 |
| MR | Monitoring | Resolved | 2022-01-01 |
| MON | Monitoring | Resolved | 2021-07-01 → 2021-07-31 |
| MON | Monitoring | Resolved | 2021-07-01 → 2021-07-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 7800 µg/L 78% of the EPA limit 10000 µg/L | 30/30 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 28/28 | LCR | 2025 |
| TTHM | 25.6 µg/L 32% of the EPA limit 80 µg/L | 8/8 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 6.7 µg/L 11% of the EPA limit 60 µg/L | 8/8 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 5200 µg/L 52% of the EPA limit 10000 µg/L | 7/7 | SYR4 | 2012–2019 |
| Bromodichloromethane | 2.5 µg/L No EPA limit set | 5/5 | SYR4 | 2015–2019 |
| Bromoform | 10.4 µg/L No EPA limit set | 5/5 | SYR4 | 2015–2019 |
| Dibromoacetic Acid | 5 µg/L No EPA limit set | 5/5 | SYR4 | 2015–2019 |
| Dibromochloromethane | 7 µg/L No EPA limit set | 5/5 | SYR4 | 2015–2019 |
| Barium | 23 µg/L 1.2% of the EPA limit 2000 µg/L | 3/3 | SYR4 | 2012–2017 |
| Fluoride | 760 µg/L 19% of the EPA limit 4000 µg/L | 3/3 | SYR4 | 2012–2017 |
| Selenium | 3 µg/L 6% of the EPA limit 50 µg/L | 3/3 | SYR4 | 2012–2017 |
| Arsenic | 1 µg/L 10% of the EPA limit 10 µg/L | 2/3 | SYR4 | 2012–2017 |
| Chromium | 3 µg/L 3% of the EPA limit 100 µg/L | 2/3 | SYR4 | 2012–2017 |
| Combined Radium (-226 And -228) | 0.3000 pCi/L 6% of the EPA limit 5 pCi/L | 2/2 | SYR4 | 2012–2014 |
| Combined Uranium | 16 µg/L 53% of the EPA limit 30 µg/L | 2/2 | SYR4 | 2012–2014 |
| Lithium | 16 µg/L No EPA limit set | 2/2 | UCMR-5 | 2023 |
| Chloroform | 0.6000 µg/L No EPA limit set | 1/5 | SYR4 | 2015–2019 |
| Gross Alpha, Excl. Radon And U | 2.9 pCi/L 19% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2012–2014 |
84 contaminants tested, none detected
Utility contact
Frequently asked questions about Lochbuie Town of
Is Lochbuie Town of tap water safe to drink?
EPA monitoring detected 23 contaminants in Lochbuie Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Lochbuie Town of's water?
EPA monitoring detected Nitrate, Lead, TTHM, Total Haloacetic Acids (HAA5), Nitrate-Nitrite, and others. The full list with the level and data source for each is above.
How many people does Lochbuie Town of serve?
Lochbuie Town of reports serving 6,518 people in Colorado, per its EPA record.
Has Lochbuie Town of had any water quality violations?
The EPA has 87 violations on file for Lochbuie Town of, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.