EPA monitoring tested this supplier for 109 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
23
detected
8,116
people served
8
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Morgan

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
78
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2009-03-01 → 2009-03-31
MCL Health-based Resolved 2009-03-01 → 2009-03-31
MCL Health-based Resolved 2009-03-01 → 2009-03-31
MCL Health-based Resolved 2009-03-01 → 2009-03-31
MCL Health-based Resolved 1997-09-01 → 1997-09-30
MCL Health-based Resolved 1997-09-01 → 1997-09-30
MCL Health-based Resolved 1997-09-01 → 1997-09-30
MCL Health-based Archived 1991-06-01 → 1991-06-30
MON Monitoring Resolved 2017-05-01 → 2017-05-31
MON Monitoring Resolved 2017-05-01 → 2017-05-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
4500 µg/L 45%
of the EPA limit 10000 µg/L
worst single sample: 4600 µg/L
58/58 SYR4 2012–2019
TTHM
23.88 µg/L 30%
of the EPA limit 80 µg/L
worst single sample: 25.2 µg/L
28/28 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
7.4555 µg/L 12%
of the EPA limit 60 µg/L
worst single sample: 8.3 µg/L
24/28 SYR4 2012–2019
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
23/23 LCR 2025
Fluoride
904 µg/L 23%
of the EPA limit 4000 µg/L
worst single sample: 1030 µg/L
15/15 SYR4 2012–2018
Barium
295.8 µg/L 15%
of the EPA limit 2000 µg/L
worst single sample: 303 µg/L
13/13 SYR4 2013–2018
Selenium
3 µg/L 6%
of the EPA limit 50 µg/L
13/13 SYR4 2013–2018
Arsenic
9.9 µg/L 99%
of the EPA limit 10 µg/L
worst single sample: 11 µg/L
12/13 SYR4 2013–2018
Bromodichloromethane
5.325 µg/L
No EPA limit set
worst single sample: 5.6 µg/L
12/15 SYR4 2012–2019
Bromoform
5.4 µg/L
No EPA limit set
12/15 SYR4 2012–2019
Dibromochloromethane
7.19 µg/L
No EPA limit set
worst single sample: 7.3 µg/L
12/15 SYR4 2012–2019
Nitrate-Nitrite
3950 µg/L 40%
of the EPA limit 10000 µg/L
worst single sample: 4500 µg/L
12/12 SYR4 2013–2019
Chromium
4 µg/L 4%
of the EPA limit 100 µg/L
worst single sample: 5 µg/L
11/13 SYR4 2013–2018
Dibromoacetic Acid
2.5 µg/L
No EPA limit set
10/10 SYR4 2015–2019
Combined Radium (-226 And -228)
0.8700 pCi/L 17%
of the EPA limit 5 pCi/L
worst single sample: 0.9000 pCi/L
7/7 SYR4 2013–2016
Combined Uranium
9.625 µg/L 32%
of the EPA limit 30 µg/L
worst single sample: 10 µg/L
6/6 SYR4 2013–2014
Lithium
21 µg/L
No EPA limit set
6/6 UCMR-5 2023
Chloroform
7.65 µg/L
No EPA limit set
worst single sample: 7.8 µg/L
4/15 SYR4 2012–2019
Dichloroacetic Acid
4.25 µg/L
No EPA limit set
worst single sample: 4.3 µg/L
3/10 SYR4 2015–2019
Trichloroacetic Acid
1.39 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
3/10 SYR4 2015–2019
Benzene
7.835 µg/L 157%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 8 µg/L
2/26 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
3.8202 pCi/L 25%
of the EPA limit 15 pCi/L
worst single sample: 3.916 pCi/L
2/6 SYR4 2013–2014
Antimony, Total
1 µg/L 17%
of the EPA limit 6 µg/L
1/13 SYR4 2013–2018
86 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAtrazineBhc-GammaBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
PFLAGER, KENT
Phone
970-867-3054
Email
KPFLAGER@MCQWD.ORG

Frequently asked questions about Morgan County Quality Wd

Is Morgan County Quality Wd tap water safe to drink?

EPA monitoring detected 23 contaminants in Morgan County Quality Wd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Morgan County Quality Wd's water?

EPA monitoring detected Nitrate, TTHM, Total Haloacetic Acids (HAA5), Lead, Fluoride, and others. The full list with the level and data source for each is above.

How many people does Morgan County Quality Wd serve?

Morgan County Quality Wd reports serving 8,116 people in Colorado, per its EPA record.

Has Morgan County Quality Wd had any water quality violations?

The EPA has 78 violations on file for Morgan County Quality Wd, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.