Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1993-01-01 → 1993-01-31 |
| MCL | Health-based | Resolved | 1993-01-01 → 1993-01-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 6.95895 µg/L 70% of the EPA limit 10 µg/L
worst single sample: 8.704 µg/L | 540/548 | SYR4 | 2012–2019 |
| Nitrate | 2644.85 µg/L 26% of the EPA limit 10000 µg/L
worst single sample: 3064 µg/L | 158/174 | SYR4 | 2012–2019 |
| Combined Uranium | 6.16219 µg/L 21% of the EPA limit 30 µg/L
worst single sample: 6.50683 µg/L | 119/145 | SYR4 | 2013–2019 |
| TTHM | 7.22 µg/L 9% of the EPA limit 80 µg/L
worst single sample: 10 µg/L | 89/176 | SYR4 | 2013–2019 |
| Tetrachloroethylene | 2.3255 µg/L 47% of the EPA limit 5 µg/L
worst single sample: 5.4 µg/L | 88/284 | SYR4 | 2012–2019 |
| Copper | 12.372 µg/L 1% of the EPA limit 1300 µg/L
worst single sample: 54.558 µg/L | 76/360 | SYR4 | 2012–2019 |
| Lead | 1.007 µg/L 6.7% of the EPA limit 15 µg/L
worst single sample: 23.543 µg/L | 76/166 | SYR4 | 2012–2019 |
| Antimony, Total | 0.1440 µg/L 2.4% of the EPA limit 6 µg/L
worst single sample: 0.1650 µg/L | 71/159 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.948 µg/L No EPA limit set
worst single sample: 4.28 µg/L | 69/176 | SYR4 | 2013–2019 |
| Chromium | 11.1746 µg/L 11% of the EPA limit 100 µg/L
worst single sample: 12.547 µg/L | 67/153 | SYR4 | 2012–2019 |
| Selenium | 2.09525 µg/L 4.2% of the EPA limit 50 µg/L
worst single sample: 2.525 µg/L | 56/128 | SYR4 | 2012–2019 |
| Bromodichloromethane | 1.78 µg/L No EPA limit set
worst single sample: 2.6 µg/L | 51/175 | SYR4 | 2013–2019 |
| Barium | 110.682 µg/L 5.5% of the EPA limit 2000 µg/L
worst single sample: 150 µg/L | 47/120 | SYR4 | 2012–2019 |
| Bromoform | 3.158 µg/L No EPA limit set
worst single sample: 3.77 µg/L | 45/175 | SYR4 | 2013–2019 |
| Cadmium | 0.1529 µg/L 3.1% of the EPA limit 5 µg/L
worst single sample: 0.1570 µg/L | 30/165 | SYR4 | 2012–2019 |
| Chloroform | 1.395 µg/L No EPA limit set
worst single sample: 2.8 µg/L | 26/176 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 2.65 µg/L No EPA limit set
worst single sample: 4.5 µg/L | 26/93 | SYR4 | 2013–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2025 |
| Beryllium, Total | 0.0122 µg/L 0.3% of the EPA limit 4 µg/L
worst single sample: 0.0140 µg/L | 13/115 | SYR4 | 2012–2019 |
| Thallium, Total | 0.0185 µg/L 0.9% of the EPA limit 2 µg/L
worst single sample: 0.0190 µg/L | 12/153 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 33 µg/L 55% of the EPA limit 60 µg/L
worst single sample: 34 µg/L | 11/93 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 1100 µg/L 11% of the EPA limit 10000 µg/L | 6/7 | SYR4 | 2016–2019 |
| Dichloroacetic Acid | 16.85 µg/L No EPA limit set
worst single sample: 17 µg/L | 4/93 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 16.85 µg/L No EPA limit set
worst single sample: 17 µg/L | 4/93 | SYR4 | 2013–2019 |
| Fluoride | 129.5 µg/L 3.2% of the EPA limit 4000 µg/L
worst single sample: 130 µg/L | 2/22 | SYR4 | 2012–2019 |
| Mercury | 0.0067 µg/L 0.3% of the EPA limit 2 µg/L
worst single sample: 0.0070 µg/L | 2/25 | SYR4 | 2012–2019 |
| cis-1,2-Dichloroethylene | 0.5000 µg/L 0.7% of the EPA limit 70 µg/L | 1/284 | SYR4 | 2012–2019 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Cal-Water Service Co.-Marysville
Is Cal-Water Service Co.-Marysville tap water safe to drink?
EPA monitoring detected 27 contaminants in Cal-Water Service Co.-Marysville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cal-Water Service Co.-Marysville's water?
EPA monitoring detected Arsenic, Nitrate, Combined Uranium, TTHM, Tetrachloroethylene, and others. The full list with the level and data source for each is above.
How many people does Cal-Water Service Co.-Marysville serve?
Cal-Water Service Co.-Marysville reports serving 12,419 people in California, per its EPA record.
Has Cal-Water Service Co.-Marysville had any water quality violations?
The EPA has 2 violations on file for Cal-Water Service Co.-Marysville, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.