← California

Tap water quality report

Pinecrest Permittees Assn

EPA monitoring tested this supplier for 54 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

54
contaminants tested
15
detected
1,298
people served
3
health-based violations
Water source
Surface water
Ownership
Private
Counties served
Tuolumne

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

3
health-based violations
10
violations on file
2
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2024-10-17
MCL Health-based Resolved 2004-04-01 → 2004-06-30
MCL Health-based Resolved 2004-01-01 → 2004-03-31
MON Monitoring Resolved 2025-04-01 → 2025-05-31
MON Monitoring Resolved 2025-04-01 → 2025-05-31
RPT Monitoring Unaddressed 2024-10-17
MR Monitoring Resolved 2005-01-01 → 2005-12-31
MR Monitoring Resolved 2005-01-01 → 2005-12-31
MR Monitoring Resolved 1993-07-01 → 2000-03-01
MR Monitoring Resolved 1993-07-01 → 2000-03-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
1272.61 µg/L 13%
of the EPA limit 10000 µg/L
worst single sample: 1516.46 µg/L
34/84 SYR4 2012–2019
Lead
0.0121 mg/L 81%
of the EPA limit 0.0150 mg/L
26/26 LCR 2025
Dichloroacetic Acid
24.8 µg/L
No EPA limit set
worst single sample: 25.1 µg/L
7/8 SYR4 2015–2018
Nitrate-Nitrite
887700 µg/L 8877%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 984000 µg/L
7/15 SYR4 2012–2016
Total Haloacetic Acids (HAA5)
73.97 µg/L 123%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 77.3 µg/L
7/8 SYR4 2015–2018
Trichloroacetic Acid
49.17 µg/L
No EPA limit set
worst single sample: 52.2 µg/L
7/8 SYR4 2015–2018
Dichloromethane
8.3675 µg/L 167%
of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 9.92 µg/L
6/10 SYR4 2015–2018
Fluoride
490.75 µg/L 12%
of the EPA limit 4000 µg/L
worst single sample: 540 µg/L
6/28 SYR4 2012–2019
Chloroform
34.48 µg/L
No EPA limit set
worst single sample: 34.8 µg/L
3/4 SYR4 2015–2018
TTHM
34.57 µg/L 43%
of the EPA limit 80 µg/L
worst single sample: 34.8 µg/L
3/4 SYR4 2015–2018
Barium
65.575 µg/L 3.3%
of the EPA limit 2000 µg/L
worst single sample: 65.8 µg/L
2/28 SYR4 2012–2019
Arsenic
4 µg/L 40%
of the EPA limit 10 µg/L
1/28 SYR4 2012–2019
Bromodichloromethane
0.9630 µg/L
No EPA limit set
1/4 SYR4 2015–2018
Copper
140 µg/L 11%
of the EPA limit 1300 µg/L
1/28 SYR4 2012–2019
Monochloroacetic Acid
1.56 µg/L
No EPA limit set
1/8 SYR4 2015–2018
39 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-DichloropropaneAntimony, TotalAsbestosAtrazineBenzeneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbon TetrachlorideChromiumDibromoacetic AcidDibromochloromethaneEthylene DibromideEthylbenzeneLassoLeadMercuryMonobromoacetic AcidNitriteSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BARCLAY, BRIAN
Phone
209-965-3234
Email
pinecrestca@yahoo.com

Frequently asked questions about Pinecrest Permittees Assn

Is Pinecrest Permittees Assn tap water safe to drink?

EPA monitoring detected 15 contaminants in Pinecrest Permittees Assn's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Pinecrest Permittees Assn's water?

EPA monitoring detected Nitrate, Lead, Dichloroacetic Acid, Nitrate-Nitrite, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Pinecrest Permittees Assn serve?

Pinecrest Permittees Assn reports serving 1,298 people in California, per its EPA record.

Has Pinecrest Permittees Assn had any water quality violations?

The EPA has 10 violations on file for Pinecrest Permittees Assn, of which 3 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.