Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-01-01 → 2025-03-31 |
| TT | Health-based | Addressed | 2024-10-17 |
| MCL | Health-based | Archived | 2021-01-01 → 2021-03-31 |
| MCL | Health-based | Archived | 2020-10-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-03-31 |
| MCL | Health-based | Resolved | 2017-10-01 → 2017-12-31 |
| MCL | Health-based | Resolved | 2017-10-01 → 2017-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 14464 µg/L 145% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 16000 µg/L | 296/316 | SYR4 | 2012–2019 |
| Arsenic | 18.25 µg/L 183% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 19 µg/L | 36/54 | SYR4 | 2012–2019 |
| Bromodichloromethane | 9.04 µg/L No EPA limit set
worst single sample: 38 µg/L | 29/30 | SYR4 | 2013–2019 |
| TTHM | 222 µg/L 278% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 290 µg/L | 29/29 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 136 µg/L 227% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 200 µg/L | 28/28 | SYR4 | 2013–2019 |
| Chloroform | 219 µg/L No EPA limit set
worst single sample: 290 µg/L | 23/28 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 88.9 µg/L No EPA limit set
worst single sample: 95 µg/L | 22/28 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 68.5 µg/L No EPA limit set
worst single sample: 110 µg/L | 22/28 | SYR4 | 2013–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 19/19 | LCR | 2025 |
| Monochloroacetic Acid | 5.775 µg/L No EPA limit set
worst single sample: 6.9 µg/L | 16/28 | SYR4 | 2013–2019 |
| 1,2-DIBROMO-3-CHLOROPROPANE | 0.0295 µg/L 15% of the EPA limit 0.2000 µg/L
worst single sample: 0.0330 µg/L | 11/26 | SYR4 | 2012–2019 |
| Fluoride | 255.5 µg/L 6.4% of the EPA limit 4000 µg/L
worst single sample: 260 µg/L | 10/18 | SYR4 | 2012–2019 |
| Bromoform | 32.9 µg/L No EPA limit set
worst single sample: 41 µg/L | 7/30 | SYR4 | 2013–2019 |
| Chromium | 41.9 µg/L 42% of the EPA limit 100 µg/L
worst single sample: 44 µg/L | 7/18 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 9.42 µg/L No EPA limit set
worst single sample: 12 µg/L | 7/28 | SYR4 | 2013–2019 |
| Dibromochloromethane | 40.1 µg/L No EPA limit set
worst single sample: 53 µg/L | 7/30 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 15000 µg/L 150% of the EPA limit, at the 95th percentile of samples — 10000 µg/L | 6/9 | SYR4 | 2017–2019 |
| Barium | 140 µg/L 7% of the EPA limit 2000 µg/L | 5/18 | SYR4 | 2012–2019 |
| Combined Uranium | 5.0362 µg/L 17% of the EPA limit 30 µg/L
worst single sample: 5.215 µg/L | 2/2 | SYR4 | 2014–2018 |
| Copper | 210 µg/L 16% of the EPA limit 1300 µg/L | 1/18 | SYR4 | 2012–2019 |
| Lead | 39 µg/L 260% of the EPA limit, at the 95th percentile of samples — 15 µg/L | 1/18 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1 µg/L No EPA limit set | 1/28 | SYR4 | 2013–2019 |
58 contaminants tested, none detected
Utility contact
Frequently asked questions about Lsid - Tonyville
Is Lsid - Tonyville tap water safe to drink?
EPA monitoring detected 22 contaminants in Lsid - Tonyville's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Lsid - Tonyville's water?
EPA monitoring detected Nitrate, Arsenic, Bromodichloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Lsid - Tonyville serve?
Lsid - Tonyville reports serving 500 people in California, per its EPA record.
Has Lsid - Tonyville had any water quality violations?
The EPA has 253 violations on file for Lsid - Tonyville, of which 239 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.