← California

Tap water quality report

Rural North Vacaville Water District

EPA monitoring tested this supplier for 74 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

74
contaminants tested
13
detected
1,313
people served
0
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Solano

Compliance record

No violations on file. The EPA has no formal drinking-water violations recorded for this supplier.

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Arsenic
16 µg/L 160%
of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 17 µg/L
52/52 SYR4 2012–2019
Nitrate
1092.46 µg/L 11%
of the EPA limit 10000 µg/L
worst single sample: 1100 µg/L
22/32 SYR4 2013–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
10/10 LCR 2025
Fluoride
357.5 µg/L 8.9%
of the EPA limit 4000 µg/L
worst single sample: 360 µg/L
6/6 SYR4 2013–2019
Combined Uranium
3.59984 µg/L 12%
of the EPA limit 30 µg/L
worst single sample: 3.64305 µg/L
5/5 SYR4 2014
Antimony, Total
0.1348 µg/L 2.2%
of the EPA limit 6 µg/L
worst single sample: 0.1350 µg/L
4/10 SYR4 2013–2019
Barium
68.5677 µg/L 3.4%
of the EPA limit 2000 µg/L
worst single sample: 69.359 µg/L
4/10 SYR4 2013–2019
Lead
0.1005 µg/L 0.7%
of the EPA limit 15 µg/L
worst single sample: 0.1050 µg/L
4/10 SYR4 2013–2019
Selenium
1.769 µg/L 3.5%
of the EPA limit 50 µg/L
worst single sample: 1.829 µg/L
4/10 SYR4 2013–2019
Nitrate-Nitrite
870 µg/L 8.7%
of the EPA limit 10000 µg/L
worst single sample: 890 µg/L
3/4 SYR4 2016–2019
Thallium, Total
0.0030 µg/L 0.2%
of the EPA limit 2 µg/L
3/9 SYR4 2013–2019
Copper
4.03 µg/L 0.3%
of the EPA limit 1300 µg/L
1/7 SYR4 2013–2019
Chromium
1.749 µg/L 1.7%
of the EPA limit 100 µg/L
1/7 SYR4 2013–2019
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromochloromethaneDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSimazineStyreneTTHMTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SWEENEY, PATRICK
Phone
707-447-8420
Email
PJSweeney@rnvwd.com

Frequently asked questions about Rural North Vacaville Water District

Is Rural North Vacaville Water District tap water safe to drink?

EPA monitoring detected 13 contaminants in Rural North Vacaville Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Rural North Vacaville Water District's water?

EPA monitoring detected Arsenic, Nitrate, Lead, Fluoride, Combined Uranium, and others. The full list with the level and data source for each is above.

How many people does Rural North Vacaville Water District serve?

Rural North Vacaville Water District reports serving 1,313 people in California, per its EPA record.

Has Rural North Vacaville Water District had any water quality violations?

The EPA has no formal drinking-water violations on file for Rural North Vacaville Water District.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.