Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 1995-03-01 → 1995-03-31 |
| TT | Health-based | Resolved | 1995-03-01 → 1995-03-31 |
| TT | Health-based | Resolved | 1995-03-01 → 1995-03-31 |
| MR | Monitoring | Resolved | 1998-01-01 → 1998-01-31 |
| MR | Monitoring | Resolved | 1998-01-01 → 1998-01-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Fluoride | 900 µg/L 23% of the EPA limit 4000 µg/L
worst single sample: 970 µg/L | 41/62 | SYR4 | 2012–2019 |
| Lead | 0.0023 mg/L 15% of the EPA limit 0.0150 mg/L | 37/37 | LCR | 2024 |
| Arsenic | 6.665 µg/L 67% of the EPA limit 10 µg/L
worst single sample: 7.9 µg/L | 30/41 | SYR4 | 2012–2019 |
| Nitrate | 4294 µg/L 43% of the EPA limit 10000 µg/L | 14/144 | SYR4 | 2012–2019 |
| Lead | 47.8 µg/L 319% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 83 µg/L | 11/44 | SYR4 | 2012–2019 |
| Chromium | 92.115 µg/L 92% of the EPA limit 100 µg/L
worst single sample: 103 µg/L | 8/43 | SYR4 | 2012–2019 |
| Combined Uranium | 2.40858 µg/L 8% of the EPA limit 30 µg/L
worst single sample: 2.831 µg/L | 8/24 | SYR4 | 2012–2019 |
| Gross Beta Particle Activity | 5.21 pCi/L No EPA limit set | 4/18 | SYR4 | 2012–2018 |
| Copper | 74 µg/L 5.7% of the EPA limit 1300 µg/L
worst single sample: 75 µg/L | 2/45 | SYR4 | 2012–2019 |
| Cadmium | 2.245 µg/L 45% of the EPA limit 5 µg/L
worst single sample: 2.3 µg/L | 2/41 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 985650 µg/L 9857% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 1000000 µg/L | 2/43 | SYR4 | 2012–2019 |
| Bromodichloromethane | 9.7 µg/L No EPA limit set | 1/1 | SYR4 | 2014 |
| Chloroform | 23 µg/L No EPA limit set | 1/1 | SYR4 | 2014 |
| Di(2-ethylhexyl) Phthalate | 3.8 µg/L 63% of the EPA limit 6 µg/L | 1/19 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.2 µg/L No EPA limit set | 1/1 | SYR4 | 2014 |
| TTHM | 36 µg/L 45% of the EPA limit 80 µg/L | 1/1 | SYR4 | 2014 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Benicia
Is City of Benicia tap water safe to drink?
EPA monitoring detected 19 contaminants in City of Benicia's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Benicia's water?
EPA monitoring detected Fluoride, Lead, Arsenic, Nitrate, Lead, and others. The full list with the level and data source for each is above.
How many people does City of Benicia serve?
City of Benicia reports serving 27,131 people in California, per its EPA record.
Has City of Benicia had any water quality violations?
The EPA has 5 violations on file for City of Benicia, of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.